Application
Direct burial in free-draining soil conditions for fixed indoor and outdoor installations. Low levels of emission of smoke and corrosive gasses in case of fire.
Construction
Cu/XLPE/LSZH/SWA/LSZH
1- Conductor: Copper
2-Insulation: XLPE
3- Filler: LSZH
4-Armour: Galvanized round steel wire
5- Outer sheath: LSZH
Technical Data
Min. bending radius 12 x D (D: Overall diameter)
Max. operating temperature 90ºC
Short circuit temperature: 250ºC
Details
| Construction | Cu/XLPE/LSZH/SWA/LSZH |
|---|---|
| Standard | BS 6724, TS IEC 60502-1 |
| UK Code | 694-B |
|
Cross-section (mm²) |
Reaction To Fire classification |
Cross-section (mm²) |
Reaction To Fire classification |
Cross-section (mm²) |
Reaction To Fire classification |
|
2×1.5 |
Dca-s2,d2,a2 |
4 x 1,5 |
Dca-s2,d2,a2 |
7 x 1,5 |
Dca-s2,d2,a2 |
|
2×2.5 |
Dca-s2,d2,a2 |
4 x 2,5 |
Dca-s2,d2,a2 |
7 x 2,5 |
Dca-s2,d2,a2 |
|
2×4 |
Dca-s2,d2,a2 |
4 x 4 |
Dca-s2,d2,a2 |
7 x 4 |
Dca-s2,d2,a2 |
|
2×6 |
Dca-s2,d2,a2 |
4 x 6 |
Dca-s2,d2,a2 |
||
|
2×10 |
Dca-s2,d2,a2 |
4 x 10 |
Dca-s2,d2,a2 |
12 x 1,5 |
Dca-s2,d2,a2 |
|
2×16 |
Dca-s2,d2,a2 |
4 x 16 |
Dca-s2,d2,a2 |
12 x 2,5 |
Dca-s2,d2,a2 |
|
2×25 |
Dca-s2,d2,a2 |
4×25 |
Dca-s2,d2,a2 |
12 x 4 |
Dca-s2,d2,a2 |
|
2×35 |
Dca-s2,d2,a2 |
4×35 |
Dca-s2,d2,a2 |
||
|
2×50 |
Dca-s2,d2,a2 |
4×50 |
Dca-s2,d2,a2 |
||
|
2×70 |
Dca-s2,d2,a2 |
4×70 |
Dca-s2,d2,a2 |
19 x 1,5 |
Dca-s2,d2,a2 |
|
2×95 |
Dca-s2,d2,a2 |
4×95 |
Dca-s2,d2,a2 |
19 x 2,5 |
Dca-s2,d2,a2 |
|
2×120 |
Dca-s2,d2,a2 |
4×120 |
Dca-s2,d2,a2 |
19 x 4 |
Dca-s2,d2,a2 |
|
2×150 |
Dca-s2,d2,a2 |
4×150 |
Dca-s2,d2,a2 |
||
|
2×185 |
Dca-s2,d2,a2 |
4×185 |
Dca-s2,d2,a2 |
||
|
2×240 |
Dca-s2,d2,a2 |
4×240 |
Dca-s2,d2,a2 |
||
|
2×300 |
Dca-s2,d2,a2 |
4×300 |
Dca-s2,d2,a2 |
||
|
3×1.5 |
Dca-s2,d2,a2 |
5 x 1,5 |
Dca-s2,d2,a2 |
||
|
3×2.5 |
Dca-s2,d2,a2 |
5 x 2,5 |
Dca-s2,d2,a2 |
||
|
3×4 |
Dca-s2,d2,a2 |
5 x 4 |
Dca-s2,d2,a2 |
||
|
3×6 |
Dca-s2,d2,a2 |
5 x 6 |
Dca-s2,d2,a2 |
||
|
3×10 |
Dca-s2,d2,a2 |
5 x 10 |
Dca-s2,d2,a2 |
||
|
3×16 |
Dca-s2,d2,a2 |
5 x 16 |
Dca-s2,d2,a2 |
||
|
3×25 |
Dca-s2,d2,a2 |
5 x 25 |
Dca-s2,d2,a2 |
||
|
3×35 |
Dca-s2,d2,a2 |
5 x 35 |
Dca-s2,d2,a2 |
||
|
3×50 |
Dca-s2,d2,a2 |
5 x 50 |
Dca-s2,d2,a2 |
||
|
3×70 |
Dca-s2,d2,a2 |
5 x 70 |
Dca-s2,d2,a2 |
||
|
3×95 |
Dca-s2,d2,a2 |
||||
|
3×120 |
Dca-s2,d2,a2 |
||||
|
3×150 |
Dca-s2,d2,a2 |
||||
|
3×185 |
Dca-s2,d2,a2 |
||||
|
3×240 |
Cca-s2,d2,a2 |
||||
|
3×300 |
Cca-s2,d2,a2 |


|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under armour |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
2×1.5 |
0,6 |
7,1 |
11,1 |
12,1 |
235 |
20S |
MS5 |
|
2×2.5 |
0,7 |
8,3 |
12,4 |
7,41 |
292 |
20S |
MS5 |
|
2×4 |
0,7 |
9,3 |
13,4 |
4,61 |
353 |
20S |
MS6 |
|
2×6 |
0,7 |
10,5 |
14,6 |
3,08 |
429 |
20S |
MS6 |
|
2×10 |
0,7 |
11,8 |
16,0 |
1,83 |
555 |
20 |
MS7 |
|
2×16 |
0,7 |
13,8 |
18,7 |
1,15 |
824 |
20 |
MS8 |
|
2×25 |
0,9 |
17,2 |
22,2 |
0,727 |
1141 |
25 |
MS9 |
|
2×35 |
0,9 |
19,4 |
25,2 |
0,524 |
1556 |
25 |
MS10 |
|
2×50 |
1 |
19,9 |
26,0 |
0,387 |
1622 |
25 |
MS11 |
|
2×70 |
1,1 |
23,0 |
29,3 |
0,268 |
2120 |
32 |
MS12 |
|
2×95 |
1,1 |
26,0 |
33,3 |
0,193 |
2913 |
32 |
MS14 |
|
2×120 |
1,2 |
29,0 |
36,4 |
0,153 |
3499 |
40 |
MS16 |
|
2×150 |
1,4 |
31,9 |
39,5 |
0,124 |
4146 |
40 |
MS16 |
|
2×185 |
1,6 |
35,7 |
44,6 |
0,0991 |
5339 |
50S |
MS18 |
|
2×240 |
1,7 |
40,8 |
49,9 |
0,0754 |
6667 |
50 |
MS20 |
|
2×300 |
1,8 |
44,8 |
54,1 |
0,0601 |
8036 |
63S |
MT9 |
|
2×400 |
2 |
51,0 |
60,7 |
0,0470 |
10200 |
63 |
MT10 |
|
3×1.5 |
0,6 |
7,5 |
11,5 |
12,1 |
257 |
20S |
MS5 |
|
3×2.5 |
0,7 |
8,9 |
12,9 |
7,41 |
329 |
20S |
MS6 |
|
3×4 |
0,7 |
10,0 |
14,0 |
4,61 |
398 |
20S |
MS6 |
|
3×6 |
0,7 |
11,2 |
15,3 |
3,08 |
491 |
20S |
MS7 |
|
3×10 |
0,7 |
12,7 |
17,6 |
1,83 |
746 |
20 |
MS7 |
|
3×16 |
0,7 |
14,8 |
19,8 |
1,15 |
993 |
25 |
MS8 |
|
3×25 |
0,9 |
18,6 |
24,4 |
0,727 |
1443 |
25 |
MS10 |
|
3×35 |
0,9 |
20,7 |
26,8 |
0,524 |
1804 |
32 |
MS11 |
|
3×50 |
1 |
22,5 |
28,6 |
0,387 |
2176 |
32 |
MS12 |
|
3×70 |
1,1 |
26,0 |
32,3 |
0,268 |
2871 |
32 |
MS14 |
|
3×95 |
1,1 |
29,7 |
37,1 |
0,193 |
3968 |
40 |
MS16 |
|
3×120 |
1,2 |
33,0 |
40,6 |
0,153 |
4795 |
50S |
MS16 |
|
3×150 |
1,4 |
37,1 |
45,9 |
0,124 |
6156 |
50S |
MS20 |
|
3×185 |
1,6 |
41,0 |
49,9 |
0,0991 |
7360 |
50 |
MS20 |
|
3×240 |
1,7 |
46,0 |
55,3 |
0,0754 |
9238 |
63S |
MT9 |
|
3×300 |
1,8 |
51,2 |
60,7 |
0,0601 |
11232 |
63 |
MT10 |
|
3×400 |
2 |
58,4 |
68,3 |
0,0470 |
14315 |
75S |
MT11 |
|
Nominal crosssectional area (mm²) |
Minimum number of wires in the conductor |
Maximum resistance of conductor at 20°C |
|||||||
|
Circular |
Circular Compacted |
Shaped |
Annealed copper conductor |
Aluminium or aluminium alloy conductor |
|||||
|
Cu |
Al |
Cu |
Al |
Cu |
Al |
Plain wires |
Metal-coated wires |
||
|
1,5 |
7 |
– |
6 |
– |
– |
– |
12,1 |
12,2 |
|
|
2,5 |
7 |
– |
6 |
– |
– |
– |
7,41 |
7,56 |
|
|
4 |
7 |
– |
6 |
– |
– |
– |
4,61 |
4,7 |
|
|
6 |
7 |
– |
6 |
– |
– |
– |
3,08 |
3,11 |
|
|
10 |
7 |
7 |
6 |
6 |
– |
– |
1,83 |
1,84 |
3,08 |
|
16 |
7 |
7 |
6 |
6 |
– |
– |
1,15 |
1,16 |
1,91 |
|
25 |
7 |
7 |
6 |
6 |
6 |
6 |
0,727 |
0,734 |
1,2 |
|
35 |
7 |
7 |
6 |
6 |
6 |
6 |
0,524 |
0,529 |
0,868 |
|
50 |
19 |
19 |
6 |
6 |
6 |
6 |
0,387 |
0,391 |
0,641 |
|
70 |
19 |
19 |
12 |
12 |
12 |
12 |
0,268 |
0,27 |
0,443 |
|
95 |
19 |
19 |
15 |
15 |
15 |
15 |
0,193 |
0,195 |
0,32 |
|
120 |
37 |
37 |
18 |
15 |
18 |
15 |
0,153 |
0,154 |
0,253 |
|
150 |
37 |
37 |
18 |
15 |
18 |
15 |
0,124 |
0,126 |
0,206 |
|
185 |
37 |
37 |
30 |
30 |
30 |
30 |
0,0991 |
0,1 |
0,164 |
|
240 |
37 |
37 |
34 |
34 |
34 |
34 |
0,0754 |
0,0762 |
0,125 |
|
300 |
61 |
61 |
34 |
34 |
34 |
34 |
0,0601 |
0,0607 |
0,1 |
|
400 |
61 |
61 |
53 |
53 |
53 |
53 |
0,047 |
0,0475 |
0,0778 |
| The above table is in accordance with BS EN 60228 | |||||||||
|
Conductor cross- sectional area |
Reference Method C |
Reference Method E |
Reference Method D |
|||
|
Clipped direct |
In free air or on a perforated cable tray etc, horizantal or vertical |
Direct in ground or in ducting in ground, in or around building |
||||
|
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
|
|
1,5 |
27 |
23 |
29 |
25 |
25 |
21 |
|
2,5 |
36 |
31 |
39 |
33 |
33 |
28 |
|
4 |
49 |
42 |
52 |
44 |
43 |
36 |
|
6 |
62 |
53 |
66 |
56 |
53 |
44 |
|
10 |
85 |
73 |
90 |
78 |
71 |
58 |
|
16 |
110 |
94 |
115 |
99 |
91 |
75 |
|
25 |
146 |
124 |
152 |
131 |
116 |
96 |
|
35 |
180 |
154 |
188 |
162 |
139 |
115 |
|
50 |
219 |
187 |
228 |
197 |
164 |
135 |
|
70 |
279 |
238 |
291 |
251 |
203 |
167 |
|
95 |
338 |
289 |
354 |
304 |
239 |
197 |
|
120 |
392 |
335 |
410 |
353 |
271 |
223 |
|
150 |
451 |
386 |
472 |
406 |
306 |
251 |
|
185 |
515 |
441 |
539 |
463 |
343 |
281 |
|
240 |
607 |
520 |
636 |
546 |
395 |
324 |
|
300 |
698 |
599 |
732 |
628 |
446 |
365 |
|
400 |
787 |
673 |
847 |
728 |
– |
– |
| The above table is in accordance with BS 7671:2018 | ||||||
|
Conductor cross- sectional area |
Two core cable DC |
Two core cable,single phase AC |
Three or four core cable,three phase AC |
||||
|
mV/A/m |
mV/A/m |
mV/A/m |
|||||
|
1,5 |
31 |
31 |
27 |
||||
|
2,5 |
19 |
19 |
16 |
||||
|
4 |
12 |
12 |
10 |
||||
|
6 |
7,9 |
7,9 |
6,8 |
||||
|
10 |
4,7 |
4,7 |
4,0 |
||||
|
16 |
2,9 |
2,9 |
2,5 |
||||
|
r |
x |
z |
r |
x |
z |
||
|
25 |
1,85 |
1,85 |
0,160 |
1,90 |
1,60 |
0,140 |
1,65 |
|
35 |
1,35 |
1,35 |
0,155 |
1,35 |
1,15 |
0,135 |
1,15 |
|
50 |
0,98 |
0,99 |
0,155 |
1,00 |
0,86 |
0,135 |
0,87 |
|
70 |
0,67 |
0,67 |
0,150 |
0,69 |
0,59 |
0,130 |
0,60 |
|
95 |
0,49 |
0,50 |
0,150 |
0,52 |
0,43 |
0,130 |
0,45 |
|
120 |
0,39 |
0,40 |
0,145 |
0,42 |
0,34 |
0,130 |
0,37 |
|
150 |
0,31 |
0,32 |
0,145 |
0,35 |
0,28 |
0,125 |
0,30 |
|
185 |
0,25 |
0,26 |
0,145 |
0,29 |
0,22 |
0,125 |
0,26 |
|
240 |
0,195 |
0,20 |
0,140 |
0,24 |
0,175 |
0,125 |
0,21 |
|
300 |
0,155 |
0,16 |
0,140 |
0,21 |
0,140 |
0,120 |
0,185 |
|
400 |
0,120 |
0,13 |
0,140 |
0,190 |
0,115 |
0,120 |
0,165 |
| The above table is in accordance with BS 7671:2018 | |||||||