YVC7V / NYCY
0.6 /1 kV PVC insulated multi-core cables with concentric conductor screen
| -20/+70 °C |

Application
Mainly laid underground in populated areas. In case of mechanical damage the screen prevents any damage due to power leak to the surrounding area.
Construction
Cu/PVC/PVC/CS/PVC
1- Conductor: Copper
2-Insulation: PVC
2-Filler: PVC
2-Concentric Screen: Copper
3- Outer sheath: PVC
Technical Data
Min. bending radius 12 x D (D: Overall diameter)
Max. operating temperature 70 ºC
Short circuit temperature: 160ºC
Details
| Construction | Cu/PVC/PVC/CS/PVC |
|---|---|
| Standard | TS IEC 60502-1, VDE 0276-603 |
|
Cross-section (mm²) |
Reaction To Fire classification |
|
3 x 1.5/1.5 |
Eca |
|
3 x 2.5/2.5 |
Eca |
|
3 x 4/4 |
Eca |
|
3 x 6/6 |
Eca |
|
3 x 10/10 |
Eca |
|
3 x 16/16 |
Eca |
|
3 x 25/16 |
Eca |
|
3 x 35/16 |
Eca |
|
3 x 50/25 |
Eca |
|
3 x 70/35 |
Eca |
|
3 x 95/50 |
Eca |
|
3 x 120/70 |
Eca |
|
3 x 150/70 |
Eca |
|
3 x 185/95 |
Eca |
|
3 x 240/120 |
Eca |
|
3 x 300/150 |
Eca |
|
3 x 400/185 |
Eca |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under armour |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
3 x 1.5/1.5 |
0,8 |
6,9 |
13,0 |
12,1 |
240 |
20S |
MS6 |
|
3 x 2.5/2.5 |
0,8 |
7,7 |
13,5 |
7,41 |
300 |
20S |
MS6 |
|
3 x 4/4 |
1 |
9,6 |
15,5 |
4,61 |
400 |
20S |
MS7 |
|
3 x 6/6 |
1 |
10,6 |
16,5 |
3,08 |
520 |
20S |
MS7 |
|
3 x 10/10 |
1 |
12,9 |
19,0 |
1,83 |
720 |
20 |
MS8 |
|
3 x 16/16 |
1 |
15,1 |
22,0 |
1,15 |
1030 |
25 |
MS9 |
|
3 x 25/16 |
1,2 |
19,5 |
25,0 |
0,727 |
1450 |
25 |
MS10 |
|
3 x 35/16 |
1,2 |
21,7 |
27,0 |
0,524 |
1800 |
32 |
MS11 |
|
3 x 50/25 |
1,4 |
25,4 |
31,0 |
0,387 |
2400 |
32 |
MS14 |
|
3 x 70/35 |
1,4 |
28,7 |
35,0 |
0,268 |
3250 |
40 |
MS14 |
|
3 x 95/50 |
1,6 |
33,6 |
41,0 |
0,193 |
4350 |
50S |
MS18 |
|
3 x 120/70 |
1,6 |
36,9 |
44,0 |
0,153 |
5400 |
50S |
MS18 |
|
3 x 150/70 |
1,8 |
40,8 |
48,0 |
0,124 |
6500 |
50 |
MS20 |
|
3 x 185/95 |
2 |
45,5 |
53,0 |
0,0991 |
8100 |
63S |
MT9 |
|
3 x 240/120 |
2,2 |
51,7 |
60,0 |
0,0754 |
10400 |
63 |
MT10 |
|
3 x 300/150 |
2,4 |
58,0 |
66,0 |
0,0601 |
13000 |
75S |
MT11 |
|
3 x 400/185 |
2,6 |
64,3 |
74,0 |
0,047 |
16400 |
75 |
MT12 |
|
Nominal crosssectional area (mm²) |
Minimum number of wires in the conductor |
Maximum resistance of conductor at 20°C |
|||||||
|
Circular |
Circular Compacted |
Shaped |
Annealed copper conductor |
Aluminium or aluminium alloy conductor |
|||||
|
Cu |
Al |
Cu |
Al |
Cu |
Al |
Plain wires |
Metal-coated wires |
||
|
1,5 |
7 |
– |
6 |
– |
– |
– |
12,1 |
12,2 |
|
|
2,5 |
7 |
– |
6 |
– |
– |
– |
7,41 |
7,56 |
|
|
4 |
7 |
– |
6 |
– |
– |
– |
4,61 |
4,7 |
|
|
6 |
7 |
– |
6 |
– |
– |
– |
3,08 |
3,11 |
|
|
10 |
7 |
7 |
6 |
6 |
– |
– |
1,83 |
1,84 |
3,08 |
|
16 |
7 |
7 |
6 |
6 |
– |
– |
1,15 |
1,16 |
1,91 |
|
25 |
7 |
7 |
6 |
6 |
6 |
6 |
0,727 |
0,734 |
1,2 |
|
35 |
7 |
7 |
6 |
6 |
6 |
6 |
0,524 |
0,529 |
0,868 |
|
50 |
19 |
19 |
6 |
6 |
6 |
6 |
0,387 |
0,391 |
0,641 |
|
70 |
19 |
19 |
12 |
12 |
12 |
12 |
0,268 |
0,27 |
0,443 |
|
95 |
19 |
19 |
15 |
15 |
15 |
15 |
0,193 |
0,195 |
0,32 |
|
120 |
37 |
37 |
18 |
15 |
18 |
15 |
0,153 |
0,154 |
0,253 |
|
150 |
37 |
37 |
18 |
15 |
18 |
15 |
0,124 |
0,126 |
0,206 |
|
185 |
37 |
37 |
30 |
30 |
30 |
30 |
0,0991 |
0,1 |
0,164 |
|
240 |
37 |
37 |
34 |
34 |
34 |
34 |
0,0754 |
0,0762 |
0,125 |
|
300 |
61 |
61 |
34 |
34 |
34 |
34 |
0,0601 |
0,0607 |
0,1 |
|
400 |
61 |
61 |
53 |
53 |
53 |
53 |
0,047 |
0,0475 |
0,0778 |
| The above table is in accordance with BS EN 60228 | |||||||||
|
Conductor cross- sectional area |
Reference Method A |
Reference Method C |
Reference Method E |
|||
|
Enclosed in Conduit in thermally insulating wall etc. |
Clipped Direct, |
In free air or on a perforated cable tray etc, horizantal or vertical |
||||
|
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
|
|
1,5 |
14 |
13 |
19,5 |
17,5 |
22 |
18,5 |
|
2,5 |
18,5 |
17,5 |
27 |
24 |
30 |
25 |
|
4 |
25 |
23 |
36 |
32 |
40 |
34 |
|
6 |
32 |
29 |
46 |
41 |
51 |
43 |
|
10 |
43 |
39 |
63 |
57 |
70 |
60 |
|
16 |
57 |
52 |
85 |
76 |
94 |
80 |
|
25 |
75 |
68 |
112 |
96 |
119 |
101 |
|
35 |
92 |
83 |
138 |
119 |
148 |
126 |
|
50 |
110 |
99 |
168 |
144 |
180 |
153 |
|
70 |
139 |
125 |
213 |
184 |
232 |
196 |
|
95 |
167 |
150 |
258 |
223 |
282 |
238 |
|
120 |
192 |
172 |
299 |
259 |
328 |
276 |
|
150 |
219 |
196 |
344 |
299 |
379 |
319 |
|
185 |
248 |
223 |
392 |
341 |
434 |
364 |
|
240 |
291 |
261 |
461 |
403 |
514 |
430 |
|
300 |
334 |
298 |
530 |
464 |
593 |
497 |
|
400 |
– |
– |
634 |
557 |
715 |
597 |
| The above table is in accordance with BS 7671:2018 | ||||||
|
Conductor cross- sectional area |
Two core cable DC |
Two core cable,single phase AC |
Three or four core cable,three phase AC |
||||
|
mV/A/m |
mV/A/m |
mV/A/m |
|||||
|
1,5 |
29 |
29 |
25 |
||||
|
2,5 |
18 |
18 |
15 |
||||
|
4 |
11 |
11 |
9,5 |
||||
|
6 |
7,3 |
7,3 |
6,4 |
||||
|
10 |
4,4 |
4,4 |
3,8 |
||||
|
16 |
2,8 |
2,8 |
2,4 |
||||
|
r |
x |
z |
r |
x |
z |
||
|
25 |
1,75 |
1,75 |
0,170 |
1,75 |
1,50 |
0,145 |
1,5 |
|
35 |
1,25 |
1,25 |
0,165 |
1,25 |
1,10 |
0,145 |
1,1 |
|
50 |
0,93 |
0,93 |
0,165 |
0,94 |
0,80 |
0,140 |
0,81 |
|
70 |
0,63 |
0,63 |
0,160 |
0,65 |
0,55 |
0,140 |
0,57 |
|
95 |
0,46 |
0,47 |
0,155 |
0,5 |
0,41 |
0,135 |
0,43 |
|
120 |
0,36 |
0,38 |
0,155 |
0,41 |
0,33 |
0,135 |
0,35 |
|
150 |
0,29 |
0,30 |
0,155 |
0,34 |
0,26 |
0,130 |
0,29 |
|
185 |
0,23 |
0,25 |
0,150 |
0,29 |
0,21 |
0,130 |
0,25 |
|
240 |
0,18 |
0,190 |
0,150 |
0,24 |
0,165 |
0,130 |
0,21 |
|
300 |
0,145 |
0,155 |
0,145 |
0,21 |
0,135 |
0,130 |
0,185 |
|
400 |
0,105 |
0,115 |
0,145 |
0,185 |
0,1 |
0,125 |
0,16 |
| The above table is in accordance with BS 7671:2018 | |||||||