YVZ2V / NYRY
0.6 /1 kV PVC insulated steel wire armoured multi-core power cables
| 20/+70 °C | Resistance to Impact |

Application
Direct burial in free-draining soil conditions for fixed indoor and outdoor installations.
Construction
Cu/PVC/PVC/SWA/PVC
1- Conductor: Copper
2-Insulation: PVC
3-Filler: PVC
4-Armour: Galvanized round steel wires
5-Outer Sheath : PVC
Technical Data
Min. bending radius 12 x D (D: Overall diameter)
Max. operating temperature 70ºC
Cross section < 300 mm² 160ºC
Cross section > 300 mm² 140ºC
Details
| Construction | Cu/PVC/PVC/SWA/PVC |
|---|---|
| Standard | TS IEC 60502-1, VDE 0271 |
|
Cross-section (mm²) |
Reaction To Fire classification |
|
2×1,5 |
Eca |
|
2×2,5 |
Eca |
|
2×4 |
Eca |
|
2×6 |
Eca |
|
2×10 |
Eca |
|
3×1,5 |
Eca |
|
3×2,5 |
Eca |
|
3×4 |
Eca |
|
3×6 |
Eca |
|
3×10 |
Eca |
|
4×1,5 |
Eca |
|
4×2,5 |
Eca |
|
4×4 |
Eca |
|
4×6 |
Eca |
|
4×10 |
Eca |
|
5×1,5 |
Eca |
|
5×2,5 |
Eca |
|
5×4 |
Eca |
|
5×6 |
Eca |
|
5×10 |
Eca |

|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under armour |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
2×1,5 |
0,8 |
7,6 |
12,9 |
12,1 |
305 |
20S |
MS6 |
|
2×2,5 |
0,8 |
8,4 |
13,8 |
7,41 |
356 |
20S |
MS6 |
|
2×4 |
1 |
10,2 |
16,3 |
4,61 |
534 |
20 |
MS7 |
|
2×6 |
1 |
11,4 |
17,4 |
3,08 |
619 |
20 |
MS7 |
|
2×10 |
1 |
12,9 |
18,9 |
1,83 |
762 |
20 |
MS8 |
|
3×1,5 |
0,8 |
8,1 |
13,5 |
12,1 |
339 |
20S |
MS6 |
|
3×2,5 |
0,8 |
9,0 |
14,4 |
7,41 |
399 |
20S |
MS6 |
|
3×4 |
1 |
11,0 |
17,0 |
4,61 |
594 |
20 |
MS7 |
|
3×6 |
1 |
12,4 |
18,4 |
3,08 |
714 |
20 |
MS8 |
|
3×10 |
1 |
14,0 |
20,1 |
1,83 |
904 |
25 |
MS8 |
|
4×1,5 |
0,8 |
8,9 |
14,3 |
12,1 |
380 |
20S |
MS6 |
|
4×2,5 |
0,8 |
9,9 |
15,3 |
7,41 |
451 |
20S |
MS7 |
|
4×4 |
1 |
12,1 |
18,2 |
4,61 |
686 |
20 |
MS8 |
|
4×6 |
1 |
13,7 |
19,8 |
3,08 |
827 |
20 |
MS8 |
|
4×10 |
1 |
15,6 |
22,3 |
1,83 |
1165 |
25 |
MS9 |
|
5×1,5 |
0,8 |
9,8 |
15,2 |
12,1 |
437 |
20S |
MS6 |
|
5×2,5 |
0,8 |
10,8 |
17,0 |
7,41 |
585 |
20 |
MS7 |
|
5×4 |
1 |
13,4 |
19,4 |
4,61 |
773 |
20 |
MS8 |
|
5×6 |
1 |
15,1 |
21,9 |
3,08 |
1047 |
25 |
MS9 |
|
5×10 |
1 |
17,2 |
23,9 |
1,83 |
1344 |
25 |
MS10 |
|
Nominal crosssectional area (mm²) |
Minimum number of wires in the conductor |
Maximum resistance of conductor at 20°C |
|||||||
|
Circular |
Circular Compacted |
Shaped |
Annealed copper conductor |
Aluminium or aluminium alloy conductor |
|||||
|
Cu |
Al |
Cu |
Al |
Cu |
Al |
Plain wires |
Metal-coated wires |
||
|
1,5 |
7 |
– |
6 |
– |
– |
– |
12,1 |
12,2 |
|
|
2,5 |
7 |
– |
6 |
– |
– |
– |
7,41 |
7,56 |
|
|
4 |
7 |
– |
6 |
– |
– |
– |
4,61 |
4,7 |
|
|
6 |
7 |
– |
6 |
– |
– |
– |
3,08 |
3,11 |
|
|
10 |
7 |
7 |
6 |
6 |
– |
– |
1,83 |
1,84 |
3,08 |
|
16 |
7 |
7 |
6 |
6 |
– |
– |
1,15 |
1,16 |
1,91 |
|
25 |
7 |
7 |
6 |
6 |
6 |
6 |
0,727 |
0,734 |
1,2 |
|
35 |
7 |
7 |
6 |
6 |
6 |
6 |
0,524 |
0,529 |
0,868 |
|
50 |
19 |
19 |
6 |
6 |
6 |
6 |
0,387 |
0,391 |
0,641 |
|
70 |
19 |
19 |
12 |
12 |
12 |
12 |
0,268 |
0,27 |
0,443 |
|
95 |
19 |
19 |
15 |
15 |
15 |
15 |
0,193 |
0,195 |
0,32 |
|
120 |
37 |
37 |
18 |
15 |
18 |
15 |
0,153 |
0,154 |
0,253 |
|
150 |
37 |
37 |
18 |
15 |
18 |
15 |
0,124 |
0,126 |
0,206 |
|
185 |
37 |
37 |
30 |
30 |
30 |
30 |
0,0991 |
0,1 |
0,164 |
|
240 |
37 |
37 |
34 |
34 |
34 |
34 |
0,0754 |
0,0762 |
0,125 |
|
300 |
61 |
61 |
34 |
34 |
34 |
34 |
0,0601 |
0,0607 |
0,1 |
|
400 |
61 |
61 |
53 |
53 |
53 |
53 |
0,047 |
0,0475 |
0,0778 |
| The above table is in accordance with BS EN 60228 | |||||||||
|
Conductor cross- sectional area |
Reference Method C |
Reference Method E |
Reference Method D |
|||
|
Clipped Direct |
In free air or on a perforated cable tray etc, horizantal or vertical |
Direct in ground or in ducting in ground, in or around buildings |
||||
|
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
|
|
1,5 |
21 |
18 |
22 |
19 |
22 |
18 |
|
2,5 |
28 |
25 |
31 |
26 |
29 |
24 |
|
4 |
38 |
33 |
41 |
35 |
37 |
30 |
|
6 |
49 |
42 |
53 |
45 |
46 |
38 |
|
10 |
67 |
58 |
72 |
62 |
60 |
50 |
|
16 |
89 |
77 |
97 |
83 |
78 |
64 |
|
25 |
118 |
102 |
128 |
110 |
99 |
82 |
|
35 |
145 |
125 |
157 |
135 |
119 |
98 |
|
50 |
175 |
151 |
190 |
163 |
140 |
116 |
|
70 |
222 |
192 |
241 |
207 |
173 |
143 |
|
95 |
269 |
231 |
291 |
251 |
204 |
169 |
|
120 |
310 |
267 |
336 |
290 |
231 |
192 |
|
150 |
356 |
306 |
386 |
332 |
261 |
217 |
|
185 |
405 |
348 |
439 |
378 |
292 |
243 |
|
240 |
476 |
409 |
516 |
445 |
336 |
280 |
|
300 |
547 |
469 |
592 |
510 |
379 |
316 |
|
400 |
621 |
540 |
683 |
590 |
– |
– |
| The above table is in accordance with BS 7671:2018 | ||||||
|
Conductor cross- sectional area |
Two core cable DC |
Two core cable,single phase AC |
Three or four core cable,three phase AC |
||||
|
mV/A/m |
mV/A/m |
mV/A/m |
|||||
|
1,5 |
29 |
29 |
25 |
||||
|
2,5 |
18 |
18 |
15 |
||||
|
4 |
11 |
11 |
9,5 |
||||
|
6 |
7,3 |
7,3 |
6,4 |
||||
|
10 |
4,4 |
4,4 |
3,8 |
||||
|
16 |
2,8 |
2,8 |
2,4 |
||||
|
r |
x |
z |
r |
x |
z |
||
|
25 |
1,75 |
1,75 |
0,170 |
1,75 |
1,50 |
0,145 |
1,5 |
|
35 |
1,25 |
1,25 |
0,165 |
1,25 |
1,10 |
0,145 |
1,1 |
|
50 |
0,93 |
0,93 |
0,165 |
0,94 |
0,80 |
0,140 |
0,81 |
|
70 |
0,63 |
0,63 |
0,160 |
0,65 |
0,55 |
0,140 |
0,57 |
|
95 |
0,46 |
0,47 |
0,155 |
0,5 |
0,41 |
0,135 |
0,43 |
|
120 |
0,36 |
0,38 |
0,155 |
0,41 |
0,33 |
0,135 |
0,35 |
|
150 |
0,29 |
0,30 |
0,155 |
0,34 |
0,26 |
0,130 |
0,29 |
|
185 |
0,23 |
0,25 |
0,150 |
0,29 |
0,21 |
0,130 |
0,25 |
|
240 |
0,18 |
0,190 |
0,150 |
0,24 |
0,165 |
0,130 |
0,21 |
|
300 |
0,145 |
0,155 |
0,145 |
0,21 |
0,135 |
0,130 |
0,185 |
|
400 |
0,105 |
0,115 |
0,145 |
0,185 |
0,1 |
0,125 |
0,16 |
| The above table is in accordance with BS 7671:2018 | |||||||