N2XRH FE 180
0.6/1 kV fire resistant, armoured, power cables
| -20/+90 °C | Flame Retardant IEC 60332-1-2 | Halogen Free IEC 60754-1 |
| Low Toxicity IEC 60754-1 | Low Corrosivity IEC… |

Application
Direct burial in free-draining soil conditions for fixed indoor and outdoor installations. Low levels of emission of smoke and corrosive gasses in case of fire. Fire resistant.
Construction
Cu/MT/XLPE/LSZH/SWA/LSZH
1- Conductor : Copper
2-Fire proof : Mica Tape
2-Insulation : XLPE
3- Filler : LSZH
4-Armour : Galvanized round steel wire
5- Outer sheath: LSZH
Technical Data
Min. bending radius 12 x D (D: Overall diameter)
Max. operating temperature 90ºC
Short circuit temperature: 250ºC
Details
| Construction | Cu/MT/XLPE/LSZH/SWA/LSZH |
|---|---|
| Standard | TS IEC 60502-1 / VDE 0276 |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under armour |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
|
1×1,5 |
0,70 |
5,1 |
9,9 |
12,1 |
185 |
|
1×2,5 |
0,70 |
5,5 |
10,4 |
7,41 |
204 |
|
1×4 |
0,70 |
6,0 |
10,9 |
4,61 |
234 |
|
1×6 |
0,70 |
6,6 |
11,4 |
3,08 |
270 |
|
1×10 |
0,70 |
7,2 |
12,1 |
1,83 |
324 |
|
1×16 |
0,70 |
8,2 |
13,1 |
1,15 |
399 |
|
1×25 |
0,90 |
9,7 |
14,6 |
0,727 |
527 |
|
1×35 |
0,90 |
10,7 |
15,6 |
0,524 |
640 |
|
1×50 |
1,00 |
12,4 |
17,9 |
0,387 |
882 |
|
1×70 |
1,10 |
14,1 |
19,6 |
0,268 |
1123 |
|
1×95 |
1,10 |
16,3 |
21,8 |
0,193 |
1425 |
|
1×120 |
1,20 |
18,1 |
24,3 |
0,153 |
1818 |
|
1×150 |
1,40 |
19,9 |
26,1 |
0,124 |
2163 |
|
1×185 |
1,60 |
21,9 |
28,1 |
0,0991 |
2568 |
|
1×240 |
1,70 |
25,0 |
31,4 |
0,0754 |
3214 |
|
1×300 |
1,80 |
27,6 |
34,0 |
0,0601 |
3878 |
|
1×400 |
2,00 |
30,9 |
38,5 |
0,047 |
5023 |
|
2×1,5 |
0,70 |
8,7 |
13,6 |
12,1 |
335 |
|
2×2,5 |
0,70 |
9,5 |
14,4 |
7,41 |
382 |
|
2×4 |
0,70 |
10,5 |
15,4 |
4,61 |
449 |
|
2×6 |
0,70 |
11,7 |
16,6 |
3,08 |
523 |
|
2×10 |
0,70 |
13,0 |
18,6 |
1,83 |
742 |
|
2×16 |
0,70 |
15,0 |
20,6 |
1,15 |
945 |
|
2×25 |
0,90 |
18,4 |
24,7 |
0,727 |
1419 |
|
2×35 |
0,90 |
20,6 |
26,9 |
0,524 |
1720 |
|
2×50 |
1,00 |
23,7 |
30,0 |
0,387 |
2148 |
|
2×70 |
1,10 |
27,1 |
33,8 |
0,268 |
2782 |
|
2×95 |
1,10 |
30,9 |
38,6 |
0,193 |
3781 |
|
2×120 |
1,20 |
34,5 |
42,4 |
0,153 |
4547 |
|
2×150 |
1,40 |
37,8 |
45,9 |
0,124 |
5391 |
|
2×185 |
1,60 |
42,1 |
51,5 |
0,0991 |
6917 |
|
2×240 |
1,70 |
47,9 |
57,7 |
0,0754 |
8620 |
|
2×300 |
1,80 |
53,5 |
63,5 |
0,0601 |
10488 |
|
2×400 |
2,00 |
59,6 |
70,2 |
0,047 |
12839 |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under armour |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
|
3 x 1,5 |
0,7 |
11,0 |
14,1 |
12,1 |
362 |
|
3 x 2,5 |
0,7 |
11,9 |
15,0 |
7,41 |
423 |
|
3 x 4 |
0,7 |
13,0 |
16,1 |
4,61 |
504 |
|
3 x 6 |
0,7 |
14,3 |
17,4 |
3,08 |
600 |
|
3 x 10 |
0,7 |
16,5 |
19,6 |
1,83 |
862 |
|
3 x 16 |
0,7 |
18,5 |
21,6 |
1,15 |
1111 |
|
3 x 25 |
0,9 |
23,1 |
26,2 |
0,727 |
1567 |
|
3 x 35 |
0,9 |
25,2 |
28,3 |
0,524 |
1923 |
|
3×50 |
1 |
28,6 |
31,9 |
0,387 |
2423 |
|
3×70 |
1,1 |
33,0 |
36,5 |
0,268 |
3342 |
|
3×95 |
1,1 |
37,1 |
41,0 |
0,193 |
4331 |
|
3×120 |
1,2 |
41,0 |
45,1 |
0,153 |
5194 |
|
3×150 |
1,4 |
46,0 |
50,5 |
0,124 |
6683 |
|
3×185 |
1,6 |
50,2 |
54,9 |
0,0991 |
8039 |
|
3×240 |
1,7 |
56,4 |
61,5 |
0,0754 |
9992 |
|
3×300 |
1,8 |
62,4 |
67,9 |
0,0601 |
12224 |
|
3×400 |
2 |
69,0 |
74,9 |
0,047 |
14934 |
|
4 x 1,5 |
0,7 |
12,0 |
15,1 |
12,1 |
407 |
|
4 x 2,5 |
0,7 |
13,0 |
16,1 |
7,41 |
478 |
|
4 x 4 |
0,7 |
14,2 |
17,3 |
4,61 |
578 |
|
4 x 6 |
0,7 |
16,4 |
19,5 |
3,08 |
796 |
|
4 x 10 |
0,7 |
18,0 |
21,1 |
1,83 |
1002 |
|
4 x 16 |
0,7 |
21,0 |
24,1 |
1,15 |
1437 |
|
4×25 |
0,9 |
25,2 |
28,3 |
0,727 |
1907 |
|
4×35 |
0,9 |
27,6 |
30,9 |
0,524 |
2363 |
|
4×50 |
1 |
31,4 |
34,9 |
0,387 |
3020 |
|
4×70 |
1,1 |
36,5 |
40,4 |
0,268 |
4220 |
|
4×95 |
1,1 |
40,8 |
44,9 |
0,193 |
5413 |
|
4×120 |
1,2 |
46,6 |
51,1 |
0,153 |
7007 |
|
4×150 |
1,4 |
50,6 |
55,3 |
0,124 |
8345 |
|
4×185 |
1,6 |
55,3 |
60,4 |
0,0991 |
10075 |
|
4×240 |
1,7 |
62,7 |
68,2 |
0,0754 |
12756 |
|
4×300 |
1,8 |
69,0 |
74,9 |
0,0601 |
15538 |
|
4×400 |
2 |
78,0 |
84,5 |
0,047 |
20030 |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under armour |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
|
5 x 1,5 |
0,7 |
11,2 |
16,1 |
12,1 |
460 |
|
5 x 2,5 |
0,7 |
12,3 |
17,2 |
7,41 |
544 |
|
5 x 4 |
0,7 |
13,7 |
19,3 |
4,61 |
756 |
|
5 x 6 |
0,7 |
15,3 |
20,9 |
3,08 |
907 |
|
5 x 10 |
0,7 |
17,2 |
22,7 |
1,83 |
1169 |
|
5 x 16 |
0,7 |
20,2 |
26,5 |
1,15 |
1634 |
|
5 x 25 |
0,9 |
24,4 |
30,6 |
0,727 |
2234 |
|
5 x 35 |
0,9 |
27,1 |
33,5 |
0,524 |
2813 |
|
5×50 |
1 |
31,6 |
39,2 |
0,387 |
3878 |
|
5×70 |
1,1 |
36,2 |
44,2 |
0,268 |
5068 |
|
5×95 |
1,1 |
41,0 |
50,4 |
0,193 |
6912 |
|
5×120 |
1,2 |
46,3 |
55,9 |
0,153 |
8422 |
|
5×150 |
1,4 |
50,8 |
60,7 |
0,124 |
10081 |
|
5×185 |
1,6 |
56,0 |
66,4 |
0,0991 |
12214 |
|
5×240 |
1,7 |
64,2 |
75,0 |
0,0754 |
15507 |
|
5×300 |
1,8 |
71,3 |
83,7 |
0,0601 |
19749 |
|
5×400 |
2 |
79,9 |
93,1 |
0,047 |
24434 |
|
7×1,5 |
0,7 |
12,3 |
17,1 |
12,1 |
508 |
|
7×2,5 |
0,7 |
13,5 |
19,1 |
7,41 |
703 |
|
7×4 |
0,7 |
15,0 |
20,6 |
4,61 |
852 |
|
7×6 |
0,7 |
16,8 |
22,4 |
3,08 |
1038 |
|
7×10 |
0,7 |
19,1 |
25,3 |
1,83 |
1488 |
|
12×1,5 |
0,7 |
16,5 |
22,0 |
12,1 |
838 |
|
12×2,5 |
0,7 |
18,2 |
23,8 |
7,41 |
1003 |
|
12×4 |
0,7 |
20,5 |
26,8 |
4,61 |
1387 |
|
12×6 |
0,7 |
22,9 |
29,1 |
3,08 |
1708 |
|
19×1,5 |
0,7 |
19,7 |
25,2 |
12,1 |
1099 |
|
19×2,5 |
0,7 |
21,8 |
28,0 |
7,41 |
1480 |
|
19×4 |
0,7 |
24,3 |
30,5 |
4,61 |
1850 |

|
Nominal crosssectional area (mm²) |
Minimum number of wires in the conductor |
Maximum resistance of conductor at 20°C |
|||||||
|
Circular |
Circular Compacted |
Shaped |
Annealed copper conductor |
Aluminium or aluminium alloy conductor |
|||||
|
Cu |
Al |
Cu |
Al |
Cu |
Al |
Plain wires |
Metal-coated wires |
||
|
1,5 |
7 |
– |
6 |
– |
– |
– |
12,1 |
12,2 |
|
|
2,5 |
7 |
– |
6 |
– |
– |
– |
7,41 |
7,56 |
|
|
4 |
7 |
– |
6 |
– |
– |
– |
4,61 |
4,7 |
|
|
6 |
7 |
– |
6 |
– |
– |
– |
3,08 |
3,11 |
|
|
10 |
7 |
7 |
6 |
6 |
– |
– |
1,83 |
1,84 |
3,08 |
|
16 |
7 |
7 |
6 |
6 |
– |
– |
1,15 |
1,16 |
1,91 |
|
25 |
7 |
7 |
6 |
6 |
6 |
6 |
0,727 |
0,734 |
1,2 |
|
35 |
7 |
7 |
6 |
6 |
6 |
6 |
0,524 |
0,529 |
0,868 |
|
50 |
19 |
19 |
6 |
6 |
6 |
6 |
0,387 |
0,391 |
0,641 |
|
70 |
19 |
19 |
12 |
12 |
12 |
12 |
0,268 |
0,27 |
0,443 |
|
95 |
19 |
19 |
15 |
15 |
15 |
15 |
0,193 |
0,195 |
0,32 |
|
120 |
37 |
37 |
18 |
15 |
18 |
15 |
0,153 |
0,154 |
0,253 |
|
150 |
37 |
37 |
18 |
15 |
18 |
15 |
0,124 |
0,126 |
0,206 |
|
185 |
37 |
37 |
30 |
30 |
30 |
30 |
0,0991 |
0,1 |
0,164 |
|
240 |
37 |
37 |
34 |
34 |
34 |
34 |
0,0754 |
0,0762 |
0,125 |
|
300 |
61 |
61 |
34 |
34 |
34 |
34 |
0,0601 |
0,0607 |
0,1 |
|
400 |
61 |
61 |
53 |
53 |
53 |
53 |
0,047 |
0,0475 |
0,0778 |
| The above table is in accordance with BS EN 60228 | |||||||||
|
Conductor cross- sectional area |
Reference Method C |
Reference Method E |
Reference Method D |
|||
|
Clipped direct |
In free air or on a perforated cable tray etc, horizantal or vertical |
Direct in ground or in ducting in ground, in or around building |
||||
|
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
|
|
1,5 |
27 |
23 |
29 |
25 |
25 |
21 |
|
2,5 |
36 |
31 |
39 |
33 |
33 |
28 |
|
4 |
49 |
42 |
52 |
44 |
43 |
36 |
|
6 |
62 |
53 |
66 |
56 |
53 |
44 |
|
10 |
85 |
73 |
90 |
78 |
71 |
58 |
|
16 |
110 |
94 |
115 |
99 |
91 |
75 |
|
25 |
146 |
124 |
152 |
131 |
116 |
96 |
|
35 |
180 |
154 |
188 |
162 |
139 |
115 |
|
50 |
219 |
187 |
228 |
197 |
164 |
135 |
|
70 |
279 |
238 |
291 |
251 |
203 |
167 |
|
95 |
338 |
289 |
354 |
304 |
239 |
197 |
|
120 |
392 |
335 |
410 |
353 |
271 |
223 |
|
150 |
451 |
386 |
472 |
406 |
306 |
251 |
|
185 |
515 |
441 |
539 |
463 |
343 |
281 |
|
240 |
607 |
520 |
636 |
546 |
395 |
324 |
|
300 |
698 |
599 |
732 |
628 |
446 |
365 |
|
400 |
787 |
673 |
847 |
728 |
– |
– |
| The above table is in accordance with BS 7671:2018 | ||||||
|
Conductor cross- sectional area |
Two core cable DC |
Two core cable,single phase AC |
Three or four core cable,three phase AC |
||||
|
mV/A/m |
mV/A/m |
mV/A/m |
|||||
|
1,5 |
31 |
31 |
27 |
||||
|
2,5 |
19 |
19 |
16 |
||||
|
4 |
12 |
12 |
10 |
||||
|
6 |
7,9 |
7,9 |
6,8 |
||||
|
10 |
4,7 |
4,7 |
4,0 |
||||
|
16 |
2,9 |
2,9 |
2,5 |
||||
|
r |
x |
z |
r |
x |
z |
||
|
25 |
1,85 |
1,85 |
0,160 |
1,90 |
1,60 |
0,140 |
1,65 |
|
35 |
1,35 |
1,35 |
0,155 |
1,35 |
1,15 |
0,135 |
1,15 |
|
50 |
0,98 |
0,99 |
0,155 |
1,00 |
0,86 |
0,135 |
0,87 |
|
70 |
0,67 |
0,67 |
0,150 |
0,69 |
0,59 |
0,130 |
0,60 |
|
95 |
0,49 |
0,50 |
0,150 |
0,52 |
0,43 |
0,130 |
0,45 |
|
120 |
0,39 |
0,40 |
0,145 |
0,42 |
0,34 |
0,130 |
0,37 |
|
150 |
0,31 |
0,32 |
0,145 |
0,35 |
0,28 |
0,125 |
0,30 |
|
185 |
0,25 |
0,26 |
0,145 |
0,29 |
0,22 |
0,125 |
0,26 |
|
240 |
0,195 |
0,20 |
0,140 |
0,24 |
0,175 |
0,125 |
0,21 |
|
300 |
0,155 |
0,16 |
0,140 |
0,21 |
0,140 |
0,120 |
0,185 |
|
400 |
0,120 |
0,13 |
0,140 |
0,190 |
0,115 |
0,120 |
0,165 |
| The above table is in accordance with BS 7671:2018 | |||||||