Application
Installation in walls, on boards and in channels or embedded in plaster. Low level of emission of smoke and corrosive gasses in case of fire.
Construction
Cu/XLPE/LSZH
1- Conductor: Flexible Copper
2-Insulation: XLPE
3- Outer sheath: LSZH
Technical Data
Min. bending radius 3 x D
Max. operating temperature 90ºC
Short circuit temperature: 250ºC
Details
| Construction | Cu/XLPE/LSZH |
|---|
|
Cross-section (mm²) |
Reaction To Fire classification |
Cross-section (mm²) |
Reaction To Fire classification |
|
1×0,5 |
Eca |
4×0,75 |
Eca |
|
1×0,75 |
Eca |
4×1 |
Eca |
|
1×1 |
Eca |
4×1,5 |
Eca |
|
1×1,5 |
Eca |
4×2,5 |
Eca |
|
1×2,5 |
Eca |
4×4 |
Eca |
|
1×4 |
Eca |
4×6 |
Eca |
|
1×6 |
Eca |
4×10 |
Eca |
|
1×10 |
Eca |
4×16 |
Eca |
|
1×16 |
Eca |
||
|
2×0,5 |
Eca |
5×0,5 |
Eca |
|
2×0,75 |
Eca |
5×0,75 |
Eca |
|
2×1 |
Eca |
5×1 |
Eca |
|
2×1,5 |
Eca |
5×1,5 |
Eca |
|
2×2,5 |
Eca |
5×2,5 |
Eca |
|
2×4 |
Eca |
5×4 |
Eca |
|
2×6 |
Eca |
5×6 |
Eca |
|
2×10 |
Eca |
5×10 |
Eca |
|
2×16 |
Eca |
5×16 |
Eca |
|
Eca |
|||
|
3×0,5 |
Eca |
||
|
3×0,75 |
Eca |
||
|
3×1 |
Eca |
||
|
3×1,5 |
Eca |
||
|
3×2,5 |
Eca |
||
|
3×4 |
Eca |
||
|
3×6 |
Eca |
||
|
3×10 |
Eca |
||
|
3×16 |
Eca |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under sheath |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
|
1×0,5 |
0,6 |
2,1 |
4,9 |
39 |
36 |
|
1×0,75 |
0,6 |
2,3 |
5,1 |
26 |
41 |
|
1×1 |
0,6 |
2,5 |
5,3 |
19,5 |
45 |
|
1×1,5 |
0,6 |
2,7 |
5,5 |
13,3 |
53 |
|
1×2,5 |
0,7 |
3,4 |
6,2 |
7,98 |
71 |
|
1×4 |
0,7 |
3,9 |
6,7 |
4,95 |
94 |
|
1×6 |
0,7 |
4,5 |
7,3 |
3,3 |
122 |
|
1×10 |
0,73 |
5,5 |
8,7 |
1,91 |
186 |
|
1×16 |
0,7 |
7,0 |
10,2 |
1,21 |
269 |
|
2×0,5 |
0,6 |
5,2 |
8,0 |
39 |
83 |
|
2×0,75 |
0,6 |
5,6 |
8,4 |
26 |
94 |
|
2×1 |
0,6 |
5,9 |
8,7 |
19,5 |
103 |
|
2×1,5 |
0,6 |
6,4 |
9,2 |
13,3 |
120 |
|
2×2,5 |
0,7 |
7,7 |
10,5 |
7,98 |
162 |
|
2×4 |
0,7 |
8,8 |
11,6 |
4,95 |
211 |
|
2×6 |
0,7 |
9,9 |
12,7 |
3,3 |
270 |
|
2×10 |
0,73 |
12,3 |
15,5 |
1,91 |
421 |
|
2×16 |
0,7 |
15,4 |
18,6 |
1,21 |
604 |
|
3×0,5 |
0,6 |
5,6 |
8,4 |
39 |
90 |
|
3×0,75 |
0,6 |
6,0 |
8,8 |
26 |
103 |
|
3×1 |
0,6 |
6,3 |
9,1 |
19,5 |
115 |
|
3×1,5 |
0,6 |
6,9 |
9,7 |
13,3 |
136 |
|
3×2,5 |
0,7 |
8,3 |
11,1 |
7,98 |
185 |
|
3×4 |
0,7 |
9,5 |
12,3 |
4,95 |
246 |
|
3×6 |
0,7 |
10,7 |
13,9 |
3,3 |
335 |
|
3×10 |
0,73 |
13,3 |
16,5 |
1,91 |
508 |
|
3×16 |
0,7 |
17,0 |
18,4 |
1,21 |
823 |
|
4×0,5 |
0,6 |
6,1 |
8,9 |
39 |
116 |
|
4×0,75 |
0,6 |
6,5 |
9,3 |
26 |
134 |
|
4×1 |
0,6 |
6,9 |
9,7 |
19,5 |
151 |
|
4×1,5 |
0,6 |
7,2 |
10,0 |
13,3 |
154 |
|
4×2,5 |
0,7 |
8,7 |
11,5 |
7,98 |
212 |
|
4×4 |
0,7 |
9,7 |
12,9 |
4,95 |
297 |
|
4×6 |
0,7 |
11,3 |
14,5 |
3,3 |
404 |
|
4×10 |
0,7 |
13,4 |
16,6 |
1,91 |
593 |
|
4×16 |
0,7 |
18,7 |
21,9 |
1,21 |
930 |
|
5×0,5 |
0,6 |
6,7 |
9,5 |
39 |
117 |
|
5×0,75 |
0,6 |
7,2 |
10,0 |
26 |
136 |
|
5×1 |
0,6 |
7,6 |
10,4 |
19,5 |
154 |
|
5×1,5 |
0,6 |
8,0 |
10,8 |
13,3 |
179 |
|
5×2,5 |
0,7 |
9,5 |
12,3 |
7,98 |
249 |
|
5×4 |
0,7 |
11,1 |
14,3 |
4,95 |
365 |
|
5×6 |
0,7 |
12,5 |
15,7 |
3,3 |
480 |
|
5×10 |
0,7 |
14,7 |
17,9 |
1,91 |
711 |
|
5×16 |
0,7 |
19,0 |
22,6 |
1,21 |
1080 |
|
Nominal crosssectional area (mm²) |
Minimum number of wires in the conductor |
Maximum resistance of conductor at 20°C |
|||||||
|
Circular |
Circular Compacted |
Shaped |
Annealed copper conductor |
Aluminium or aluminium alloy conductor |
|||||
|
Cu |
Al |
Cu |
Al |
Cu |
Al |
Plain wires |
Metal-coated wires |
||
|
1,5 |
7 |
– |
6 |
– |
– |
– |
12,1 |
12,2 |
– |
|
2,5 |
7 |
– |
6 |
– |
– |
– |
7,41 |
7,56 |
– |
|
4 |
7 |
– |
6 |
– |
– |
– |
4,61 |
4,7 |
– |
|
6 |
7 |
– |
6 |
– |
– |
– |
3,08 |
3,11 |
– |
|
10 |
7 |
7 |
6 |
6 |
– |
– |
1,83 |
1,84 |
3,08 |
|
16 |
7 |
7 |
6 |
6 |
– |
– |
1,15 |
1,16 |
1,91 |
| The above table is in accordance with BS EN 60228 | |||||||||
|
Conductor cross- sectional area |
Reference Method A |
Reference Method C |
Reference Method E |
|||
|
Enclosed in Conduit in thermally insulating wall etc. |
Clipped Direct, |
In free air or on a perforated cable tray etc, horizantal or vertical |
||||
|
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
|
|
1,5 |
13 |
12 |
19 |
17 |
21 |
18 |
|
2,5 |
18 |
17 |
26 |
23 |
29 |
24 |
|
4 |
24 |
22 |
34 |
30 |
38 |
32 |
|
6 |
30 |
37 |
44 |
39 |
48 |
41 |
|
10 |
41 |
49 |
60 |
54 |
67 |
57 |
|
16 |
54 |
65 |
81 |
72 |
89 |
76 |
| The above table is in accordance with BS 7671:2018 | ||||||
|
Conductor cross- sectional area |
Two core cable DC |
Two core cable,single phase AC |
Three or four core cable,three phase AC |
||||
|
mV/A/m |
mV/A/m |
mV/A/m |
|||||
|
1,5 |
31,9 |
31,9 |
27,5 |
||||
|
2,5 |
19,8 |
19,8 |
16,5 |
||||
|
4 |
12,1 |
12,1 |
10,5 |
||||
|
6 |
8,0 |
8,0 |
7,0 |
||||
|
10 |
4,8 |
4,8 |
4,2 |
||||
|
16 |
3,1 |
3,1 |
2,6 |
||||
| The above table is in accordance with BS 7671:2018 | |||||||