YMvK-ss
0.6/1 kV XLPE insulated power cables
| -20/+90 °C | Flame Retardant IEC 60332-1-2 | Flame Retardant IEC 60332-3-24 | Flexible |

Application
Installation in walls, on boards and in channels or embedded in plaster.
Construction
Cu/XLPE/PVC
1- Conductor: Flexible Copper (Class-2)
2-Insulation: XLPE
3- Filler: PVC
4- Outer sheath: PVC
Technical Data
Min. bending radius 15 x D
Max. operating temperature 90ºC
Short circuit temperature: 250ºC
Details
| Construction | Cu/XLPE/PVC |
|---|---|
| Standard | HD 604 PART 4 SECTION D |
|
Cross-section (mm²) |
Reaction To Fire classification |
Cross-section (mm²) |
Reaction To Fire classification |
Cross-section (mm²) |
Reaction To Fire classification |
|
1×10 |
Dca-s2,d2,a3 |
3 x 10 |
Dca-s2,d2,a3 |
5 x 10 |
Dca-s2,d2,a3 |
|
1×16 |
Dca-s2,d2,a3 |
3 x 16 |
Dca-s2,d2,a3 |
5 x 16 |
Dca-s2,d2,a3 |
|
1×25 |
Dca-s2,d2,a3 |
3 x 25 |
Dca-s2,d2,a3 |
5 x 25 |
Dca-s2,d2,a3 |
|
1×35 |
Dca-s2,d2,a3 |
3 x 35 |
Dca-s2,d2,a3 |
5 x 35 |
Dca-s2,d2,a3 |
|
1×50 |
Dca-s2,d2,a3 |
3×50 |
Dca-s2,d2,a3 |
5×50 |
Dca-s2,d2,a3 |
|
1×70 |
Dca-s2,d2,a3 |
3×70 |
Dca-s2,d2,a3 |
5×70 |
Dca-s2,d2,a3 |
|
1×95 |
Dca-s2,d2,a3 |
3×95 |
Dca-s2,d2,a3 |
5×95 |
Dca-s2,d2,a3 |
|
1×120 |
Dca-s2,d2,a3 |
3×120 |
Dca-s2,d2,a3 |
5×120 |
Dca-s2,d2,a3 |
|
1×150 |
Dca-s2,d2,a3 |
3×150 |
Dca-s2,d2,a3 |
5×150 |
Dca-s2,d2,a3 |
|
1×185 |
Dca-s2,d2,a3 |
3×185 |
Dca-s2,d2,a3 |
5×185 |
Dca-s2,d2,a3 |
|
1×240 |
Dca-s2,d2,a3 |
3×240 |
Dca-s2,d2,a3 |
5×240 |
Dca-s2,d2,a3 |
|
1×300 |
Dca-s2,d2,a3 |
||||
|
2×10 |
Dca-s2,d2,a3 |
4 x 10 |
Dca-s2,d2,a3 |
||
|
2×16 |
Dca-s2,d2,a3 |
4 x 16 |
Dca-s2,d2,a3 |
||
|
2×25 |
Dca-s2,d2,a3 |
4×25 |
Dca-s2,d2,a3 |
||
|
2×35 |
Dca-s2,d2,a3 |
4×35 |
Dca-s2,d2,a3 |
||
|
2×50 |
Dca-s2,d2,a3 |
4×50 |
Dca-s2,d2,a3 |
||
|
2×70 |
Dca-s2,d2,a3 |
4×70 |
Dca-s2,d2,a3 |
||
|
2×95 |
Dca-s2,d2,a3 |
4×95 |
Dca-s2,d2,a3 |
||
|
2×120 |
Dca-s2,d2,a3 |
4×120 |
Dca-s2,d2,a3 |
||
|
2×150 |
Dca-s2,d2,a3 |
4×150 |
Dca-s2,d2,a3 |
||
|
2×185 |
Dca-s2,d2,a3 |
4×185 |
Dca-s2,d2,a3 |
||
|
2×240 |
Dca-s2,d2,a3 |
4×240 |
Dca-s2,d2,a3 |

|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under sheath |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
1×10 |
0,7 |
5,4 |
8,2 |
1,83 |
145 |
20S |
MS4 |
|
1×16 |
0,7 |
6,4 |
9,2 |
1,15 |
206 |
20S |
MS4 |
|
1×25 |
0,9 |
8,1 |
10,9 |
0,727 |
309 |
20S |
MS5 |
|
1×35 |
0,9 |
9,2 |
12,0 |
0,524 |
403 |
20S |
MS5 |
|
1×50 |
1 |
10,9 |
13,7 |
0,387 |
530 |
20S |
MS6 |
|
1×70 |
1,1 |
12,7 |
15,5 |
0,268 |
736 |
20 |
MS7 |
|
1×95 |
1,1 |
16,0 |
19,0 |
0,193 |
1026 |
25 |
MS8 |
|
1×120 |
1,2 |
18,2 |
21,2 |
0,153 |
1266 |
25 |
MS9 |
|
1×150 |
1,4 |
20,6 |
23,8 |
0,124 |
1595 |
32 |
MS10 |
|
1×185 |
1,6 |
22,7 |
25,9 |
0,0991 |
1970 |
32 |
MS11 |
|
1×240 |
1,7 |
25,9 |
29,3 |
0,0754 |
2555 |
32 |
MS12 |
|
1×300 |
1,8 |
29,4 |
33,0 |
0,0601 |
3157 |
40 |
MS14 |
|
2×10 |
0,7 |
11,3 |
14,9 |
1,83 |
419 |
20S |
MS6 |
|
2×16 |
0,7 |
13,4 |
17,0 |
1,15 |
591 |
20 |
MS7 |
|
2×25 |
0,9 |
17,9 |
21,5 |
0,727 |
777 |
25 |
MS9 |
|
2×35 |
0,9 |
20,1 |
23,7 |
0,524 |
983 |
32 |
MS10 |
|
2×50 |
1 |
23,5 |
27,1 |
0,387 |
1266 |
32 |
MS11 |
|
2×70 |
1,1 |
27,1 |
30,7 |
0,268 |
1714 |
40 |
MS14 |
|
2×95 |
1,1 |
33,9 |
37,7 |
0,193 |
2379 |
50S |
MS16 |
|
2×120 |
1,2 |
38,3 |
42,5 |
0,153 |
2944 |
50 |
MS18 |
|
2×150 |
1,4 |
43,1 |
47,5 |
0,124 |
3654 |
50 |
MS20 |
|
2×185 |
1,6 |
47,7 |
52,3 |
0,0991 |
4554 |
63S |
MT9 |
|
2×240 |
1,7 |
54,1 |
59,1 |
0,0754 |
5842 |
63 |
MT10 |
|
3 x 10 |
0,7 |
12,1 |
15,7 |
1,83 |
508 |
20 |
MS7 |
|
3 x 16 |
0,7 |
14,4 |
18,0 |
1,15 |
731 |
25 |
MS8 |
|
3 x 25 |
0,9 |
19,2 |
22,8 |
0,727 |
1044 |
25 |
MS9 |
|
3 x 35 |
0,9 |
21,6 |
25,2 |
0,524 |
1338 |
32 |
MS10 |
|
3×50 |
1 |
25,2 |
28,8 |
0,387 |
1742 |
32 |
MS12 |
|
3×70 |
1,1 |
29,1 |
32,9 |
0,268 |
2402 |
40 |
MS14 |
|
3×95 |
1,1 |
36,4 |
40,4 |
0,193 |
3339 |
50S |
MS16 |
|
3×120 |
1,2 |
41,2 |
45,4 |
0,153 |
4122 |
50 |
MS18 |
|
3×150 |
1,4 |
46,8 |
50,5 |
0,124 |
5233 |
63S |
MS20 |
|
3×185 |
1,6 |
51,3 |
56,0 |
0,0991 |
6453 |
63 |
MT9 |
|
3×240 |
1,7 |
58,2 |
63,0 |
0,0754 |
8306 |
75S |
MT10 |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under armour |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
4 x 10 |
0,7 |
13,5 |
17,1 |
1,83 |
620 |
20 |
MS7 |
|
4 x 16 |
0,7 |
16,0 |
19,6 |
1,15 |
899 |
25 |
MS8 |
|
4×25 |
0,9 |
21,3 |
24,9 |
0,727 |
1319 |
32 |
MS10 |
|
4×35 |
0,9 |
23,9 |
27,5 |
0,524 |
1717 |
32 |
MS11 |
|
4×50 |
1 |
28,1 |
31,9 |
0,387 |
2265 |
40 |
MS14 |
|
4×70 |
1,1 |
32,6 |
36,6 |
0,268 |
3177 |
50S |
MS16 |
|
4×95 |
1,1 |
40,6 |
44,8 |
0,193 |
4375 |
50 |
MS18 |
|
4×120 |
1,2 |
46,3 |
50,9 |
0,153 |
5507 |
63S |
MT9 |
|
4×150 |
1,4 |
52,1 |
56,0 |
0,124 |
6875 |
63 |
MT9 |
|
4×185 |
1,6 |
57,2 |
62,4 |
0,0991 |
8514 |
75S |
MT10 |
|
4×240 |
1,7 |
65,2 |
70,5 |
0,0754 |
11060 |
75 |
MT12 |
|
5 x 10 |
0,7 |
15,1 |
18,7 |
1,83 |
737 |
25 |
MS8 |
|
5 x 16 |
0,7 |
18,9 |
22,5 |
1,15 |
1135 |
25 |
MS9 |
|
5 x 25 |
0,9 |
23,6 |
27,2 |
0,727 |
1702 |
32 |
MS11 |
|
5 x 35 |
0,9 |
26,5 |
30,1 |
0,524 |
2219 |
40 |
MS12 |
|
5×50 |
1 |
31,3 |
35,3 |
0,387 |
3005 |
40 |
MS14 |
|
5×70 |
1,1 |
36,4 |
40,6 |
0,268 |
4201 |
50S |
MS16 |
|
5×95 |
1,1 |
45,3 |
49,9 |
0,193 |
5924 |
63S |
MS20 |
|
5×120 |
1,2 |
51,6 |
56,0 |
0,153 |
7423 |
63 |
MT9 |
|
5×150 |
1,4 |
58,1 |
62,0 |
0,124 |
9347 |
75S |
MT10 |
|
5×185 |
1,6 |
63,8 |
69,0 |
0,0991 |
11572 |
75 |
MT11 |
|
5×240 |
1,7 |
72,6 |
77,0 |
0,0754 |
15019 |
MT14 |
|
Conductor cross- sectional area |
Reference Method A |
Reference Method C |
Reference Method E |
|||
|
Enclosed in Conduit in thermally insulating wall etc. |
Clipped Direct, |
In free air or on a perforated cable tray etc, horizantal or vertical |
||||
|
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
|
|
1,5 |
13 |
12 |
19 |
17 |
21 |
18 |
|
2,5 |
18 |
17 |
26 |
23 |
29 |
24 |
|
4 |
24 |
22 |
34 |
30 |
38 |
32 |
|
6 |
30 |
37 |
44 |
39 |
48 |
41 |
|
10 |
41 |
49 |
60 |
54 |
67 |
57 |
|
16 |
54 |
65 |
81 |
72 |
89 |
76 |
| The above table is in accordance with BS 7671:2018 | ||||||
|
Conductor cross- sectional area |
Two core cable DC |
Two core cable,single phase AC |
Three or four core cable,three phase AC |
||||
|
mV/A/m |
mV/A/m |
mV/A/m |
|||||
|
1,5 |
31,9 |
31,9 |
27,5 |
||||
|
2,5 |
19,8 |
19,8 |
16,5 |
||||
|
4 |
12,1 |
12,1 |
10,5 |
||||
|
6 |
8,0 |
8,0 |
7,0 |
||||
|
10 |
4,8 |
4,8 |
4,2 |
||||
|
16 |
3,1 |
3,1 |
2,6 |
||||
| The above table is in accordance with BS 7671:2018 | |||||||