Application
Installation in surface mounted or embedded conduits or similar closed systems.
Construction
Cu/PVC
1- Conductor: Flexible Copper
2-Insulation: PVC
Technical Data
Min. bending radius 5 x D (D: Overall diameter)
Max. operating temperature 70 0C
Short circuit temperature: 160 0C
Details
| Construction | Cu/PVC |
|---|---|
| Standard | EN 50525-2-31 |
| UK Code | 6491X |
|
Cross-section (mm²) |
Reaction To Fire classification |
|
1,5 |
Eca |
|
2,5 |
Eca |
|
4 |
Eca |
|
6 |
Eca |
|
10 |
Eca |
|
16 |
Eca |
|
25 |
Eca |
|
35 |
Eca |
|
50 |
Eca |
|
70 |
Eca |
|
95 |
Eca |
|
120 |
Eca |
|
150 |
Eca |
|
185 |
Eca |
|
240 |
Eca |


|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
|
1,5 |
0,7 |
2,8 |
13,3 |
19,42 |
|
2,5 |
0,8 |
3,3 |
7,98 |
30,53 |
|
4 |
0,8 |
3,8 |
4,95 |
44,57 |
|
6 |
0,8 |
4,3 |
3,3 |
62,33 |
|
10 |
1 |
5,8 |
1,91 |
107,47 |
|
16 |
1 |
6,7 |
1,21 |
159,01 |
|
25 |
1,2 |
8,3 |
0,78 |
252,96 |
|
35 |
1,2 |
9,3 |
0,554 |
339,62 |
|
50 |
1,4 |
11,0 |
0,386 |
487,03 |
|
70 |
1,4 |
12,5 |
0,272 |
670,25 |
|
95 |
1,6 |
14,7 |
0,206 |
909,82 |
|
120 |
1,6 |
16,3 |
0,161 |
1140,47 |
|
150 |
1,8 |
18,0 |
0,129 |
1400,56 |
|
185 |
2 |
19,9 |
0,106 |
1762,34 |
|
240 |
2,2 |
23,0 |
0,0801 |
2203,36 |
| re: Solid Conductor | rm: Stranded Conductor | * 300/500 V |
|
Current Rating |
|||||||||
|
Conductor cross- sectional area |
Reference Method A |
Reference Method C |
Reference Method F |
||||||
|
Enclosed in Conduit in thermally insulating wall etc. |
Clipped Direct, |
In free air or on a perforated cable tray etc, horizantal or vertical |
|||||||
|
2 cables, single-phase AC or DC (A) |
Three or four cables, three-phase AC (A) |
2 cables, single-phase AC or DC flat and touching (A) |
3 o 4 cables, three-phase AC flat and touching or trefoil (A) |
Touching two cables, single-phase AC or DC flat (A) |
Touching 3 cables, three-phase AC or DC flat (A) |
Touching 3 cables, three-phase AC or DC flat (A) |
Spaced by one diameter 2 cablessingle phase AC or Dc or 3 cables 3 phase AC flat Horizantal |
Spaced by one diameter 2 cablessingle phase AC or Dc or 3 cables 3 phase AC flat Vertical |
|
|
1 |
10,5 |
10,0 |
14,7 |
13,3 |
0,0 |
0,0 |
0,0 |
0,0 |
0,0 |
|
1,5 |
13,8 |
12,8 |
19,0 |
17,1 |
0,0 |
0,0 |
0,0 |
0,0 |
0,0 |
|
2,5 |
19,0 |
17,1 |
25,7 |
23,8 |
0,0 |
0,0 |
0,0 |
0,0 |
0,0 |
|
4 |
24,7 |
22,8 |
35,2 |
31,4 |
0,0 |
0,0 |
0,0 |
0,0 |
0,0 |
|
6 |
32,3 |
29,5 |
44,7 |
40,9 |
0,0 |
0,0 |
0,0 |
0,0 |
0,0 |
|
10 |
43,7 |
39,9 |
61,8 |
56,1 |
0,0 |
0,0 |
0,0 |
0,0 |
0,0 |
|
16 |
58,0 |
53,2 |
82,7 |
75,1 |
0,0 |
0,0 |
0,0 |
0,0 |
0,0 |
|
25 |
77,6 |
70,8 |
110,6 |
100,9 |
127,1 |
110,6 |
106,7 |
141,6 |
126,1 |
|
35 |
96,0 |
86,3 |
136,8 |
125,1 |
157,1 |
138,7 |
132,9 |
175,6 |
157,1 |
|
50 |
115,4 |
104,8 |
176,5 |
162,0 |
190,1 |
168,8 |
162,0 |
212,4 |
191,1 |
|
70 |
146,5 |
131,9 |
227,0 |
207,6 |
243,5 |
218,3 |
209,5 |
272,6 |
246,4 |
|
95 |
176,5 |
159,1 |
275,5 |
253,2 |
294,9 |
266,8 |
256,1 |
330,8 |
301,7 |
|
120 |
203,7 |
182,4 |
320,1 |
293,9 |
341,4 |
311,4 |
298,8 |
384,1 |
351,1 |
|
150 |
232,8 |
209,5 |
369,6 |
338,5 |
393,8 |
360,8 |
345,3 |
442,3 |
406,4 |
|
185 |
264,8 |
237,7 |
422,9 |
388,0 |
449,1 |
414,2 |
396,7 |
505,4 |
465,6 |
|
240 |
311,4 |
277,4 |
499,6 |
457,8 |
529,6 |
491,8 |
470,5 |
596,6 |
551,9 |
|
300 |
356,0 |
318,2 |
576,2 |
528,7 |
610,1 |
569,4 |
544,2 |
687,7 |
639,2 |
|
400 |
– |
– |
673,2 |
615,0 |
731,4 |
668,3 |
636,3 |
826,4 |
771,2 |
|
500 |
– |
– |
768,2 |
701,3 |
842,0 |
765,3 |
726,5 |
952,5 |
892,4 |
|
630 |
– |
– |
876,9 |
801,2 |
974,9 |
877,9 |
829,4 |
1103,9 |
1037,9 |
| The above table is in accordance with BS 7671:2018 | |||||||||
|
Conductor cross- sectional area |
VOLTAGE DROP |
|||||||||||
|
Two cable DC |
2 Cables single phase AC |
|||||||||||
|
Reference Method A&B (enclosed in conduit or trunking) |
Reference Method C&F (clipped direct, on try or in free air) |
|||||||||||
|
Cables Touching |
Cables Spaced* |
|||||||||||
|
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
|||||||||
|
1 |
48,4 |
48,4 |
48,4 |
48,4 |
||||||||
|
1,5 |
30,8 |
31,9 |
31,9 |
31,9 |
||||||||
|
2,5 |
19,8 |
19,8 |
19,8 |
19,8 |
||||||||
|
4 |
12,1 |
12,1 |
12,1 |
12,1 |
||||||||
|
6 |
8,03 |
8,03 |
8,03 |
8,03 |
||||||||
|
10 |
4,84 |
4,84 |
4,84 |
4,84 |
||||||||
|
16 |
3,08 |
3,08 |
3,08 |
3,08 |
||||||||
|
r |
x |
z |
r |
x |
z |
r |
x |
z |
||||
|
25 |
1,855 |
1,908 |
0,3498 |
1,908 |
1,855 |
0,212 |
1,855 |
1,855 |
0,3074 |
1,908 |
||
|
35 |
1,325 |
1,378 |
0,3286 |
1,378 |
1,325 |
0,2067 |
1,325 |
1,325 |
0,2968 |
1,378 |
||
|
50 |
0,9858 |
1,007 |
0,318 |
1,06 |
0,9858 |
0,2014 |
1,007 |
0,9858 |
0,2968 |
1,0282 |
||
|
70 |
0,6678 |
0,689 |
0,3074 |
0,7632 |
0,6678 |
0,2014 |
0,6996 |
0,6678 |
0,2862 |
0,7314 |
||
|
95 |
0,4876 |
0,5194 |
0,2968 |
0,5936 |
0,4982 |
0,1908 |
0,53 |
0,4982 |
0,2862 |
0,5724 |
||
|
120 |
0,3816 |
0,4134 |
0,2862 |
0,4982 |
0,3922 |
0,1908 |
0,4346 |
0,3922 |
0,2756 |
0,477 |
||
|
150 |
0,3074 |
0,3286 |
0,2862 |
0,4346 |
0,318 |
0,1908 |
0,3604 |
0,3074 |
0,2756 |
0,4134 |
||
|
185 |
0,2438 |
0,265 |
0,2862 |
0,3922 |
0,2544 |
0,1802 |
0,3074 |
0,2544 |
0,2756 |
0,371 |
||
|
240 |
0,1908 |
0,212 |
0,2756 |
0,3498 |
0,2014 |
0,1802 |
0,265 |
0,2014 |
0,265 |
0,3286 |
||
|
300 |
0,159 |
0,1696 |
0,2756 |
0,3286 |
0,159 |
0,1802 |
0,2332 |
0,159 |
0,265 |
0,3074 |
||
|
400 |
0,1166 |
0,1378 |
0,2756 |
0,3074 |
0,1272 |
0,1696 |
0,212 |
0,1272 |
0,265 |
0,2862 |
||
|
500 |
0,09116 |
0,1166 |
0,2756 |
0,2968 |
1,0388 |
0,1643 |
0,1961 |
0,09858 |
0,2544 |
0,2756 |
||
|
630 |
0,07208 |
0,09964 |
0,265 |
0,2862 |
0,08586 |
0,1643 |
0,1855 |
0,08056 |
0,2544 |
0,265 |
||
|
Conductor cross- sectional area |
3 or 4 cables three-phase AC |
|||||||||||
|
Reference Method A&B (enclosed in conduit or trunking) |
Reference Method C&F (clipped direct, on tray or in free air |
|||||||||||
|
Cables Touching, Trefoil |
Cables Touching, Flat |
Cables spaced* , Flat |
||||||||||
|
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
|||||||||
|
1 |
41,8 |
41,8 |
41,8 |
41,8 |
||||||||
|
1,5 |
27,5 |
27,5 |
27,5 |
27,5 |
||||||||
|
2,5 |
16,5 |
16,5 |
16,5 |
16,5 |
||||||||
|
4 |
10,45 |
10,45 |
10,45 |
10,45 |
||||||||
|
6 |
7,04 |
7,04 |
7,04 |
7,04 |
||||||||
|
10 |
4,18 |
4,18 |
4,18 |
4,18 |
||||||||
|
16 |
2,64 |
2,64 |
2,64 |
2,64 |
||||||||
|
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
|
|
25 |
1,59 |
0,3074 |
1,643 |
1,59 |
0,1855 |
1,59 |
1,59 |
0,265 |
1,643 |
1,59 |
0,3392 |
1,643 |
|
35 |
1,166 |
0,2862 |
1,166 |
1,166 |
0,1802 |
1,166 |
1,166 |
0,2544 |
1,166 |
1,166 |
0,3392 |
1,219 |
|
50 |
0,8586 |
0,2756 |
0,901 |
0,848 |
0,1802 |
0,8692 |
0,848 |
0,2544 |
0,8904 |
0,848 |
0,3392 |
0,9116 |
|
70 |
0,5936 |
0,265 |
0,6466 |
0,583 |
0,1696 |
0,6042 |
0,583 |
0,2544 |
0,636 |
0,583 |
0,3286 |
0,6678 |
|
95 |
0,4452 |
0,2544 |
0,5088 |
0,4346 |
0,1696 |
0,4558 |
0,4346 |
0,2438 |
0,4982 |
0,424 |
0,3286 |
0,5406 |
|
120 |
0,3498 |
0,2438 |
0,4346 |
0,3392 |
0,159 |
0,3816 |
0,3392 |
0,2438 |
0,424 |
0,3392 |
0,318 |
0,4664 |
|
150 |
0,2862 |
0,2438 |
0,3816 |
0,2756 |
0,159 |
0,318 |
0,2756 |
0,2438 |
0,3604 |
0,2756 |
0,318 |
0,424 |
|
185 |
0,2332 |
0,2438 |
0,3392 |
0,2226 |
0,159 |
0,2756 |
0,2226 |
0,2332 |
0,3286 |
0,2226 |
0,318 |
0,3816 |
|
240 |
0,1802 |
0,2438 |
0,3074 |
0,1696 |
0,159 |
0,2332 |
0,1696 |
0,2332 |
0,2862 |
0,1696 |
0,3074 |
0,3604 |
|
300 |
0,1484 |
0,2438 |
0,2862 |
0,1378 |
0,1484 |
0,2014 |
0,1378 |
0,2332 |
0,265 |
0,1378 |
0,3074 |
0,3392 |
|
400 |
0,1272 |
0,2332 |
0,265 |
0,1166 |
0,1484 |
0,1908 |
0,1166 |
0,2226 |
0,2544 |
0,106 |
0,3074 |
0,3286 |
|
500 |
0,106 |
0,2332 |
0,265 |
0,09116 |
0,1431 |
0,1696 |
0,09116 |
0,2226 |
0,2438 |
0,08586 |
0,3074 |
0,318 |
|
630 |
0,0848 |
0,2332 |
0,2544 |
0,07632 |
0,1431 |
0,159 |
0,07632 |
0,2226 |
0,2332 |
0,06996 |
0,2968 |
0,3074 |
| * Spacings larger than one cable diameter will result in a larger voltage drop.
The above table is in accordance with BS 7671:2018 |
||||||||||||