H07Z1-K
450/750V halogen free, flame retardant, flexible cables
| -20/+90 °C | Flame Retardant IEC 60332-1-2 | Halogen Free IEC 60754-1 | Flexible |
| Low Toxicity IEC … |

Application
For protected installations in equipment and light fitting. Also for in conduit, on / or under plaster.
Construction
Cu/LSZH
1- Conductor: Flexible Copper
2-Insulation: LSZH
Technical Data
Max. operating temperature 70ºC
Short circuit temperature: 160ºC
Details
| Construction | Cu/LSZH |
|---|---|
| Standard | EN 50525-3-31 |
|
Cross-section (mm²) |
Reaction To Fire classification |
|
1,5 |
Eca |
|
2,5 |
Eca |
|
4 |
Eca |
|
6 |
Eca |
|
10 |
Dca-s2,d2,a2 |
|
16 |
Dca-s2,d2,a2 |
|
25 |
Dca-s2,d2,a2 |
|
35 |
Dca-s2,d2,a2 |
|
50 |
Dca-s2,d2,a2 |
|
70 |
Dca-s2,d2,a2 |
|
95 |
Dca-s2,d2,a2 |
|
120 |
Dca-s2,d2,a2 |
|
150 |
Dca-s2,d2,a2 |
|
185 |
Dca-s2,d2,a2 |
|
240 |
Dca-s2,d2,a2 |
|
300 |
Dca-s2,d2,a2 |
|
400 |
Dca-s2,d2,a2 |
|
500 |
Dca-s2,d2,a2 |
|
630 |
Dca-s2,d2,a2 |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
|
0.50 re* |
0,6 |
2,0 |
36 |
8 |
|
0.75 re* |
0,6 |
2,2 |
24,5 |
11 |
|
1.0 re* |
0,6 |
2,3 |
18,1 |
14 |
|
1.5 re |
0,7 |
2,8 |
12,1 |
20 |
|
2.5 re |
0,8 |
3,3 |
7,41 |
30 |
|
4 re |
0,8 |
3,8 |
4,61 |
45 |
|
6 re |
0,8 |
4,3 |
3,08 |
63 |
|
10 rm |
1 |
7,0 |
1,83 |
129 |
|
16 rm |
1 |
6,7 |
1,15 |
165 |
|
25 rm |
1,2 |
8,3 |
0,727 |
254 |
|
35 rm |
1,2 |
9,3 |
0,524 |
342 |
|
50 rm |
1,4 |
11,0 |
0,387 |
468 |
|
70 rm |
1,4 |
12,5 |
0,268 |
651 |
|
95 rm |
1,6 |
14,7 |
0,193 |
906 |
|
120 rm |
1,6 |
16,3 |
0,153 |
1123 |
|
150 rm |
1,8 |
18,0 |
0,124 |
1400 |
|
185 rm |
2 |
19,9 |
0,0991 |
1747 |
|
240 rm |
2,2 |
23,0 |
0,0754 |
2275 |
|
300 rm |
2,4 |
25,8 |
0,0601 |
2870 |
|
400 rm |
2,6 |
28,9 |
0,047 |
3618 |
|
500 rm |
2,8 |
32,1 |
0,0366 |
4694 |
|
630 rm |
2,8 |
36,2 |
0,0283 |
6049 |
| re: Solid Conductor rm: Stranded Conductor * 300/500 V | ||||

|
Conductor cross- sectional area |
Reference Method A |
Reference Method C |
Reference Method F |
||||||
|
Enclosed in Conduit in thermally insulating wall etc. |
Clipped Direct, |
In free air or on a perforated cable tray etc, horizantal or vertical |
|||||||
|
2 cables, single-phase AC or DC (A) |
Three or four cables, three-phase AC (A) |
2 cables, single-phase AC or DC flat and touching (A) |
3 o 4 cables, three-phase AC flat and touching or trefoil (A) |
Touching two cables, single-phase AC or DC flat (A) |
Touching 3 cables, three-phase AC or DC flat (A) |
Touching 3 cables, three-phase AC or DC flat (A) |
Spaced by one diameter 2 cablessingle phase AC or Dc or 3 cables 3 phase AC flat Horizantal |
Spaced by one diameter 2 cablessingle phase AC or Dc or 3 cables 3 phase AC flat Vertical |
|
|
1 |
11 |
10,5 |
15,5 |
14 |
– |
– |
– |
– |
– |
|
1,5 |
14,5 |
13,5 |
20 |
18 |
– |
– |
– |
– |
– |
|
2,5 |
20 |
18 |
27 |
25 |
– |
– |
– |
– |
– |
|
4 |
26 |
24 |
37 |
33 |
– |
– |
– |
– |
– |
|
6 |
34 |
31 |
47 |
43 |
– |
– |
– |
– |
– |
|
10 |
46 |
42 |
65 |
59 |
– |
– |
– |
– |
– |
|
16 |
61 |
56 |
87 |
79 |
– |
– |
– |
– |
– |
|
25 |
80 |
73 |
114 |
104 |
131 |
114 |
110 |
146 |
130 |
|
35 |
99 |
89 |
141 |
129 |
162 |
143 |
137 |
181 |
162 |
|
50 |
119 |
108 |
182 |
167 |
196 |
174 |
167 |
219 |
197 |
|
70 |
151 |
136 |
234 |
214 |
251 |
225 |
216 |
281 |
254 |
|
95 |
182 |
164 |
284 |
261 |
304 |
275 |
264 |
341 |
311 |
|
120 |
210 |
188 |
330 |
303 |
352 |
321 |
308 |
396 |
362 |
|
150 |
240 |
216 |
381 |
349 |
406 |
372 |
356 |
456 |
419 |
|
185 |
273 |
245 |
436 |
400 |
463 |
427 |
409 |
521 |
480 |
|
240 |
321 |
286 |
515 |
472 |
546 |
507 |
485 |
615 |
569 |
|
300 |
367 |
328 |
594 |
545 |
629 |
587 |
561 |
709 |
659 |
|
400 |
– |
– |
694 |
634 |
754 |
689 |
656 |
852 |
795 |
|
500 |
– |
– |
792 |
723 |
868 |
789 |
749 |
982 |
920 |
|
630 |
– |
– |
904 |
826 |
1005 |
905 |
855 |
1138 |
1070 |
| The above table is in accordance with BS 7671:2018 | |||||||||
|
Conductor cross- sectional area |
Two cable DC |
2 Cables single phase AC |
||||||||||
|
Reference Method A&B (enclosed in conduit or trunking) |
Reference Method C&F (clipped direct, on try or in free air) |
|||||||||||
|
Cables Touching |
Cables Spaced* |
|||||||||||
|
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
|||||||||
|
1 |
44 |
44 |
44 |
44 |
||||||||
|
1,5 |
29 |
29 |
29 |
29 |
||||||||
|
2,5 |
18 |
18 |
18 |
18 |
||||||||
|
4 |
11 |
11 |
11 |
11 |
||||||||
|
6 |
7,3 |
7,3 |
7,3 |
7,3 |
||||||||
|
10 |
4,4 |
4,4 |
4,4 |
4,4 |
||||||||
|
16 |
2,8 |
2,8 |
2,8 |
2,8 |
||||||||
|
r |
x |
z |
r |
x |
z |
r |
x |
z |
||||
|
25 |
1,75 |
1,8 |
0,33 |
1,8 |
1,75 |
0.20 |
1,75 |
1,75 |
0,29 |
1,8 |
||
|
35 |
1,25 |
1,3 |
0,31 |
1,3 |
1,25 |
0,195 |
1,25 |
1,25 |
0,28 |
1,3 |
||
|
50 |
0,93 |
0,95 |
0,3 |
1 |
0,93 |
0,19 |
0,95 |
0,93 |
0,28 |
0,97 |
||
|
70 |
0,63 |
0,65 |
0,29 |
0,72 |
0,63 |
0,19 |
0,66 |
0,63 |
0,27 |
0,69 |
||
|
95 |
0,46 |
0,49 |
0,28 |
0,56 |
0,47 |
0,18 |
0,5 |
0,47 |
0,27 |
0,54 |
||
|
120 |
0,36 |
0,39 |
0,27 |
0,47 |
0,37 |
0,18 |
0,41 |
0,37 |
0,26 |
0,45 |
||
|
150 |
0,29 |
0,31 |
0,27 |
0,41 |
0,3 |
0,18 |
0,34 |
0,29 |
0,26 |
0,39 |
||
|
185 |
0,23 |
0,25 |
0,27 |
0,37 |
0,24 |
0,17 |
0,29 |
0,24 |
0,26 |
0,35 |
||
|
240 |
0,18 |
0,2 |
0,26 |
0,33 |
0,19 |
0,17 |
0,25 |
0,19 |
0,25 |
0,31 |
||
|
300 |
0,15 |
0,16 |
0,26 |
0,31 |
0,15 |
0,17 |
0,22 |
0,15 |
0,25 |
0,29 |
||
|
400 |
0,11 |
0,13 |
0,26 |
0,29 |
0,12 |
0,16 |
0,2 |
0,12 |
0,25 |
0,27 |
||
|
500 |
0,086 |
0,11 |
0,26 |
0,28 |
0,98 |
0,155 |
0,185 |
0,093 |
0,24 |
0,26 |
||
|
630 |
0,068 |
0,094 |
0,25 |
0,27 |
0,081 |
0,155 |
0,175 |
0,076 |
0,24 |
0,25 |
||
|
Conductor cross- sectional area |
3 or 4 cables three-phase AC |
|||||||||||
|
Reference Method A&B (enclosed in conduit or trunking) |
Reference Method C&F (clipped direct, on tray or in free air |
|||||||||||
|
Cables Touching, Trefoil |
Cables Touching, Flat |
Cables spaced* , Flat |
||||||||||
|
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
|||||||||
|
1 |
38 |
38 |
38 |
38 |
||||||||
|
1,5 |
25 |
25 |
25 |
25 |
||||||||
|
2,5 |
15 |
15 |
15 |
15 |
||||||||
|
4 |
9,5 |
9,5 |
9,5 |
9,5 |
||||||||
|
6 |
6,4 |
6,4 |
6,4 |
6,4 |
||||||||
|
10 |
3,8 |
3,8 |
3,8 |
3,8 |
||||||||
|
16 |
2,4 |
2,4 |
2,4 |
2,4 |
||||||||
|
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
|
|
25 |
1,5 |
0,29 |
1,55 |
1,5 |
0,175 |
1,5 |
1,5 |
0,25 |
1,55 |
1,5 |
0,32 |
1,55 |
|
35 |
1,1 |
0,27 |
1,1 |
1,1 |
0,17 |
1,1 |
1,1 |
0,24 |
1,1 |
1,1 |
0,32 |
1,15 |
|
50 |
0,81 |
0,26 |
0,85 |
0,8 |
0,17 |
0,82 |
0,8 |
0,24 |
0,84 |
0,8 |
0,32 |
0,86 |
|
70 |
0,56 |
0,25 |
0,61 |
0,55 |
0,16 |
0,57 |
0,55 |
0,24 |
0,6 |
0,55 |
0,31 |
0,63 |
|
95 |
0,42 |
0,24 |
0,48 |
0,41 |
0,16 |
0,43 |
0,41 |
0,23 |
0,47 |
0,4 |
0,31 |
0,51 |
|
120 |
0,33 |
0,23 |
0,41 |
0,32 |
0,15 |
0,36 |
0,32 |
0,23 |
0,4 |
0,32 |
0,3 |
0,44 |
|
150 |
0,27 |
0,23 |
0,36 |
0,26 |
0,15 |
0,3 |
0,26 |
0,23 |
0,34 |
0,26 |
0,3 |
0,4 |
|
185 |
0,22 |
0,23 |
0,32 |
0,21 |
0,15 |
0,26 |
0,21 |
0,22 |
0,31 |
0,21 |
0,3 |
0,36 |
|
240 |
0,17 |
0,23 |
0,29 |
0,16 |
0,15 |
0,22 |
0,16 |
0,22 |
0,27 |
0,16 |
0,29 |
0,34 |
|
300 |
0,14 |
0,23 |
0,27 |
0,13 |
0,14 |
0,19 |
0,13 |
0,22 |
0,25 |
0,13 |
0,29 |
0,32 |
|
400 |
0,12 |
0,22 |
0,25 |
0,11 |
0,14 |
0,18 |
0,11 |
0,21 |
0,24 |
0,1 |
0,29 |
0,31 |
|
500 |
0,1 |
0,22 |
0,25 |
0,086 |
0,135 |
0,16 |
0,086 |
0,21 |
0,23 |
0,081 |
0,29 |
0,3 |
|
630 |
0,08 |
0,22 |
0,24 |
0,072 |
0,135 |
0,15 |
0,072 |
0,21 |
0,22 |
0,066 |
0,28 |
0,29 |
| * Spacings larger than one cable diameter will result in a larger voltage drop.
The above table is in accordance with BS 7671:2018 |
||||||||||||