NHMH
300/500 V PP insulated, multi-core, halogen free, flame retardant cables
| -20/+90 °C | Flame Retardant IEC 60332-1-2 | Halogen Free IEC 60754-1 |
| Low Toxicity IEC … |

Application
Installation in walls, on boards and in channels or embedded in plaster. Low level of emission of smoke and corrosive gasses in case of fire.
Construction
Cu/PP/LSZH/LSZH
1- Conductor: Copper
2-Insulation: PP
3-Filler :LSZH
4- Outer sheath: LSZH
Technical Data
Min. bending radius 12 x D (D: Overall diameter)
Max. operating temperature 70 ºC
Details
| Construction | Cu/PP/LSZH/LSZH |
|---|---|
| Standard | VDE 0250 Teil 215 |
|
Cross-section (mm²) |
Reaction To Fire classification |
Cross-section (mm²) |
Reaction To Fire classification |
|
2×1,5 |
Eca |
4×1,5 |
Eca |
|
2×2,5 |
Eca |
4×2,5 |
Eca |
|
2×4 |
Eca |
4×4 |
Eca |
|
2×6 |
Eca |
4×6 |
Eca |
|
2×10 |
Eca |
4 x 10 |
Eca |
|
2×16 |
Eca |
4 x 16 |
Eca |
|
2×25 |
Eca |
4×25 |
Eca |
|
2×35 |
Eca |
4×35 |
Eca |
|
3×1,5 |
Eca |
5×1,5 |
Eca |
|
3×2,5 |
Eca |
5×2,5 |
Eca |
|
3×4 |
Eca |
5×4 |
Eca |
|
3×6 |
Eca |
5×6 |
Eca |
|
3 x 10 |
Eca |
5 x 10 |
Eca |
|
3 x 16 |
Eca |
5 x 16 |
Eca |
|
3 x 25 |
Eca |
5 x 25 |
Eca |
|
3 x 35 |
Eca |
5 x 35 |
Eca |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under sheath |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
2×1,5 |
0,5 |
5,6 |
8,0 |
12,1 |
109 |
20S |
MS4 |
|
2×2,5 |
0,5 |
6,3 |
8,7 |
7,41 |
148 |
20S |
MS4 |
|
2×4 |
0,6 |
7,6 |
10,0 |
4,61 |
191 |
20S |
MS4 |
|
2×6 |
0,6 |
8,6 |
11,0 |
3,08 |
245 |
20S |
MS5 |
|
2×10 |
0,7 |
11,0 |
13,8 |
1,83 |
378 |
20S |
MS6 |
|
2×16 |
0,7 |
13,8 |
16,6 |
1,15 |
571 |
20 |
MS7 |
|
2×25 |
0,9 |
17,0 |
19,8 |
0,727 |
844 |
25 |
MS8 |
|
2×35 |
0,9 |
19,4 |
22,6 |
0,524 |
1134 |
25 |
MS9 |
|
3×1,5 |
0,5 |
6,0 |
8,4 |
12,1 |
126 |
20S |
MS4 |
|
3×2,5 |
0,5 |
6,8 |
9,2 |
7,41 |
173 |
20S |
MS4 |
|
3×4 |
0,6 |
8,2 |
10,6 |
4,61 |
227 |
20S |
MS5 |
|
3×6 |
0,6 |
9,3 |
12,1 |
3,08 |
310 |
20S |
MS5 |
|
3 x 10 |
0,7 |
11,8 |
14,6 |
1,83 |
465 |
20 |
MS6 |
|
3 x 16 |
0,7 |
15,3 |
18,1 |
1,15 |
728 |
25 |
MS8 |
|
3 x 25 |
0,9 |
18,3 |
21,5 |
0,727 |
1079 |
25 |
MS9 |
|
3 x 35 |
0,9 |
20,9 |
24,1 |
0,524 |
1431 |
32 |
MS10 |
|
4×1,5 |
0,5 |
6,6 |
9,0 |
12,1 |
149 |
20S |
MS4 |
|
4×2,5 |
0,5 |
7,5 |
9,9 |
7,41 |
208 |
20S |
MS4 |
|
4×4 |
0,6 |
9,1 |
11,9 |
4,61 |
290 |
20S |
MS5 |
|
4×6 |
0,6 |
10,6 |
13,4 |
3,08 |
395 |
20S |
MS6 |
|
4 x 10 |
0,7 |
13,0 |
15,8 |
1,83 |
576 |
20 |
MS7 |
|
4 x 16 |
0,7 |
16,8 |
19,6 |
1,15 |
908 |
25 |
MS8 |
|
4×25 |
0,9 |
20,6 |
23,8 |
0,727 |
1379 |
32 |
MS10 |
|
4×35 |
0,9 |
23,1 |
26,3 |
0,524 |
1803 |
32 |
MS11 |
|
5×1,5 |
0,5 |
7,2 |
9,6 |
12,1 |
174 |
20S |
MS4 |
|
5×2,5 |
0,5 |
8,3 |
10,7 |
7,41 |
245 |
20S |
MS5 |
|
5×4 |
0,6 |
10,4 |
13,2 |
4,61 |
358 |
20S |
MS6 |
|
5×6 |
0,6 |
11,7 |
14,5 |
3,08 |
470 |
20 |
MS6 |
|
5 x 10 |
0,7 |
14,4 |
17,2 |
1,83 |
692 |
25 |
MS7 |
|
5 x 16 |
0,7 |
18,6 |
21,8 |
1,15 |
1116 |
25 |
MS9 |
|
5 x 25 |
0,9 |
22,8 |
26,0 |
0,727 |
1666 |
32 |
MS11 |
|
5 x 35 |
0,9 |
25,9 |
29,1 |
0,524 |
2218 |
32 |
MS12 |
|
Nominal crosssectional area (mm²) |
Minimum number of wires in the conductor |
Maximum resistance of conductor at 20°C |
|||||||
|
Circular |
Circular Compacted |
Shaped |
Annealed copper conductor |
Aluminium or aluminium alloy conductor |
|||||
|
Cu |
Al |
Cu |
Al |
Cu |
Al |
Plain wires |
Metal-coated wires |
||
|
1,5 |
7 |
– |
6 |
– |
– |
– |
12,1 |
12,2 |
|
|
2,5 |
7 |
– |
6 |
– |
– |
– |
7,41 |
7,56 |
|
|
4 |
7 |
– |
6 |
– |
– |
– |
4,61 |
4,7 |
|
|
6 |
7 |
– |
6 |
– |
– |
– |
3,08 |
3,11 |
|
|
10 |
7 |
7 |
6 |
6 |
– |
– |
1,83 |
1,84 |
3,08 |
|
16 |
7 |
7 |
6 |
6 |
– |
– |
1,15 |
1,16 |
1,91 |
|
25 |
7 |
7 |
6 |
6 |
6 |
6 |
0,727 |
0,734 |
1,2 |
|
35 |
7 |
7 |
6 |
6 |
6 |
6 |
0,524 |
0,529 |
0,868 |
| The above table is in accordance with BS EN 60228 | |||||||||
|
Conductor cross- sectional area |
Reference Method A |
Reference Method C |
Reference Method E |
|||
|
Enclosed in Conduit in thermally insulating wall etc. |
Clipped Direct, |
In free air or on a perforated cable tray etc, horizantal or vertical |
||||
|
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
|
|
1,5 |
14 |
13 |
19,5 |
17,5 |
22 |
18,5 |
|
2,5 |
18,5 |
17,5 |
27 |
24 |
30 |
25 |
|
4 |
25 |
23 |
36 |
32 |
40 |
34 |
|
6 |
32 |
29 |
46 |
41 |
51 |
43 |
|
10 |
43 |
39 |
63 |
57 |
70 |
60 |
|
16 |
57 |
52 |
85 |
76 |
94 |
80 |
|
25 |
75 |
68 |
112 |
96 |
119 |
101 |
|
35 |
92 |
83 |
138 |
119 |
148 |
126 |
| The above table is in accordance with BS 7671:2018 | ||||||
|
Conductor cross- sectional area |
Two core cable DC |
Two core cable,single phase AC |
Three or four core cable,three phase AC |
||||
|
mV/A/m |
mV/A/m |
mV/A/m |
|||||
|
1,5 |
29 |
29 |
25 |
||||
|
2,5 |
18 |
18 |
15 |
||||
|
4 |
11 |
11 |
9,5 |
||||
|
6 |
7,3 |
7,3 |
6,4 |
||||
|
10 |
4,4 |
4,4 |
3,8 |
||||
|
16 |
2,8 |
2,8 |
2,4 |
||||
|
r |
x |
z |
r |
x |
z |
||
|
25 |
1,75 |
1,75 |
0,170 |
1,75 |
1,50 |
0,145 |
1,5 |
|
35 |
1,25 |
1,25 |
0,165 |
1,25 |
1,10 |
0,145 |
1,1 |
| The above table is in accordance with BS 7671:2018 | |||||||