XVB
0.6 /1 kV PVC power cables
| -20/+90 °C | Flame Retardant IEC 60332-1-2 | Flame Retardant IEC 60332-3-24 |

Application
Installation in walls, on boards and in channels or embedded in plaster.
Construction
Cu/XLPE/PVC
1- Conductor: Copper
2-Insulation: XLPE
3- Filler : PVC
4- Outer sheath: PVC
Technical Data
Min. bending radius 15 x D
Max. operating temperature 90 ºC
Short circuit temperature: 250 ºC
Details
| Construction | Cu/XLPE/PVC |
|---|---|
| Standard | NBN HD 604 PART 4 SECTION G |
|
Cross-section (mm²) |
Reaction To Fire classification |
Cross-section (mm²) |
Reaction To Fire classification |
|
1×25 |
Cca,s2,d2,a3 |
4×1,5 |
Cca,s2,d2,a3 |
|
1×35 |
Cca,s2,d2,a3 |
4×2,5 |
Cca,s2,d2,a3 |
|
1×50 |
Cca,s2,d2,a3 |
4×4 |
Cca,s2,d2,a3 |
|
1×70 |
Cca,s2,d2,a3 |
4×6 |
Cca,s2,d2,a3 |
|
1×95 |
Cca,s2,d2,a3 |
4 x 10 |
Cca,s2,d2,a3 |
|
1×120 |
Cca,s2,d2,a3 |
4 x 16 |
Cca,s2,d2,a3 |
|
1×150 |
Cca,s2,d2,a3 |
4×25 |
Cca,s2,d2,a3 |
|
1×185 |
Cca,s2,d2,a3 |
4×35 |
Cca,s2,d2,a3 |
|
1×240 |
Cca,s2,d2,a3 |
4×50 |
Cca,s2,d2,a3 |
|
1×300 |
Cca,s2,d2,a3 |
4×70 |
Cca,s2,d2,a3 |
|
4×95 |
Cca,s2,d2,a3 |
||
|
2×1,5 |
Cca,s2,d2,a3 |
4×120 |
Cca,s2,d2,a3 |
|
2×2,5 |
Cca,s2,d2,a3 |
4×150 |
Cca,s2,d2,a3 |
|
2×4 |
Cca,s2,d2,a3 |
4×185 |
Cca,s2,d2,a3 |
|
2×6 |
Cca,s2,d2,a3 |
4×240 |
Cca,s2,d2,a3 |
|
2×10 |
Cca,s2,d2,a3 |
4×300 |
Cca,s2,d2,a3 |
|
2×16 |
Cca,s2,d2,a3 |
||
|
2×25 |
Cca,s2,d2,a3 |
5×1,5 |
Cca,s2,d2,a3 |
|
2×35 |
Cca,s2,d2,a3 |
5×2,5 |
Cca,s2,d2,a3 |
|
5×4 |
Cca,s2,d2,a3 |
||
|
3 x 1,5 |
Cca,s2,d2,a3 |
5×6 |
Cca,s2,d2,a3 |
|
3 x 2,5 |
Cca,s2,d2,a3 |
5 x 10 |
Cca,s2,d2,a3 |
|
3 x 4 |
Cca,s2,d2,a3 |
5 x 16 |
Cca,s2,d2,a3 |
|
3 x 6 |
Cca,s2,d2,a3 |
5 x 25 |
Cca,s2,d2,a3 |
|
3 x 10 |
Cca,s2,d2,a3 |
||
|
3 x 16 |
Cca,s2,d2,a3 |
||
|
3 x 25 |
Cca,s2,d2,a3 |
||
|
3 x 35 |
Cca,s2,d2,a3 |
||
|
3×50 |
Cca,s2,d2,a3 |
||
|
3×70 |
Cca,s2,d2,a3 |
||
|
3×95 |
Cca,s2,d2,a3 |
||
|
3×120 |
Cca,s2,d2,a3 |
||
|
3×150 |
Cca,s2,d2,a3 |
||
|
3×185 |
Cca,s2,d2,a3 |
||
|
3×240 |
Cca,s2,d2,a3 |
||
|
3×300 |
Cca,s2,d2,a3 |

|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under sheath |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
1×25 |
0,9 |
7,7 |
10,5 |
0,727 |
296 |
20S |
MS5 |
|
1×35 |
0,9 |
8,7 |
11,5 |
0,524 |
389 |
20S |
MS5 |
|
1×50 |
1 |
10,1 |
12,9 |
0,387 |
513 |
20S |
MS6 |
|
1×70 |
1,1 |
11,9 |
14,7 |
0,268 |
707 |
20 |
MS6 |
|
1×95 |
1,1 |
13,6 |
16,6 |
0,193 |
962 |
20 |
MS7 |
|
1×120 |
1,2 |
15,3 |
18,3 |
0,153 |
1190 |
25 |
MS8 |
|
1×150 |
1,4 |
17,1 |
20,3 |
0,124 |
1480 |
25 |
MS9 |
|
1×185 |
1,6 |
19,0 |
22,2 |
0,0991 |
1827 |
25 |
MS9 |
|
1×240 |
1,7 |
22,0 |
25,4 |
0,0754 |
2366 |
32 |
MS11 |
|
1×300 |
1,8 |
24,0 |
27,6 |
0,0601 |
2958 |
32 |
MS11 |
|
2×1,5 |
0,7 |
6,0 |
8,8 |
12,1 |
120 |
20S |
MS4 |
|
2×2,5 |
0,7 |
6,8 |
9,6 |
7,41 |
151 |
20S |
MS4 |
|
2×4 |
0,7 |
7,7 |
10,5 |
4,61 |
196 |
20S |
MS5 |
|
2×6 |
0,7 |
8,7 |
11,5 |
3,08 |
252 |
20S |
MS5 |
|
2×10 |
0,7 |
10,3 |
13,1 |
1,83 |
359 |
20S |
MS6 |
|
2×16 |
0,7 |
12,7 |
15,5 |
1,15 |
531 |
20 |
MS7 |
|
2×25 |
0,9 |
15,8 |
19,0 |
0,727 |
810 |
25 |
MS8 |
|
2×35 |
0,9 |
18,0 |
21,2 |
0,524 |
1062 |
25 |
MS9 |
|
3 x 1,5 |
0,7 |
6,5 |
9,3 |
12,1 |
137 |
20S |
MS4 |
|
3 x 2,5 |
0,7 |
7,3 |
10,1 |
7,41 |
176 |
20S |
MS4 |
|
3 x 4 |
0,7 |
8,3 |
11,1 |
4,61 |
234 |
20S |
MS5 |
|
3 x 6 |
0,7 |
9,3 |
12,1 |
3,08 |
305 |
20S |
MS5 |
|
3 x 10 |
0,7 |
11,0 |
13,8 |
1,83 |
445 |
20S |
MS6 |
|
3 x 16 |
0,7 |
13,7 |
16,7 |
1,15 |
675 |
20 |
MS7 |
|
3 x 25 |
0,9 |
17,1 |
20,3 |
0,727 |
1024 |
25 |
MS9 |
|
3 x 35 |
0,9 |
19,3 |
22,7 |
0,524 |
1355 |
25 |
MS9 |
|
3×50 |
1 |
22,6 |
26,2 |
0,387 |
1818 |
32 |
MS11 |
|
3×70 |
1,1 |
25,9 |
29,7 |
0,268 |
2293 |
32 |
MS12 |
|
3×95 |
1,1 |
29,6 |
33,6 |
0,193 |
3095 |
40 |
MS14 |
|
3×120 |
1,2 |
32,9 |
37,1 |
0,153 |
3840 |
50S |
MS16 |
|
3×150 |
1,4 |
37,0 |
41,6 |
0,124 |
4793 |
50S |
MS18 |
|
3×185 |
1,6 |
40,9 |
45,7 |
0,0991 |
5878 |
50 |
MS18 |
|
3×240 |
1,7 |
45,9 |
51,1 |
0,0754 |
7598 |
63S |
MT9 |
|
3×300 |
1,8 |
51,1 |
56,7 |
0,0601 |
9483 |
63 |
MT9 |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under armour |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
4×1,5 |
0,7 |
7,2 |
10,0 |
12,1 |
159 |
20S |
MS4 |
|
4×2,5 |
0,7 |
8,1 |
10,9 |
7,41 |
207 |
20S |
MS5 |
|
4×4 |
0,7 |
9,2 |
12,0 |
4,61 |
279 |
20S |
MS5 |
|
4×6 |
0,7 |
10,4 |
13,2 |
3,08 |
370 |
20S |
MS6 |
|
4 x 10 |
0,7 |
12,3 |
15,3 |
1,83 |
554 |
20 |
MS7 |
|
4 x 16 |
0,7 |
15,2 |
18,2 |
1,15 |
833 |
25 |
MS8 |
|
4×25 |
0,9 |
19,0 |
22,4 |
0,727 |
1282 |
25 |
MS9 |
|
4×35 |
0,9 |
21,4 |
25,0 |
0,524 |
1704 |
32 |
MS10 |
|
4×50 |
1 |
25,2 |
28,8 |
0,387 |
2271 |
32 |
MS12 |
|
4×70 |
1,1 |
30,0 |
34,0 |
0,268 |
3028 |
40 |
MS14 |
|
4×95 |
1,1 |
34,0 |
38,2 |
0,193 |
4062 |
50S |
MS16 |
|
4×120 |
1,2 |
38,2 |
42,8 |
0,153 |
5123 |
50 |
MS18 |
|
4×150 |
1,4 |
42,5 |
47,3 |
0,124 |
6295 |
50 |
MS20 |
|
4×185 |
1,6 |
47,0 |
52,2 |
0,0991 |
7757 |
63S |
MT9 |
|
4×240 |
1,7 |
53,2 |
58,8 |
0,0754 |
10111 |
63 |
MT10 |
|
4×300 |
1,8 |
58,8 |
64,8 |
0,0601 |
12513 |
75S |
MT11 |
|
5×1,5 |
0,7 |
8,0 |
10,8 |
12,1 |
186 |
20S |
MS5 |
|
5×2,5 |
0,7 |
9,0 |
11,8 |
7,41 |
244 |
20S |
MS5 |
|
5×4 |
0,7 |
10,2 |
13,0 |
4,61 |
332 |
20S |
MS6 |
|
5×6 |
0,7 |
11,5 |
14,3 |
3,08 |
443 |
20S |
MS6 |
|
5 x 10 |
0,7 |
13,7 |
16,7 |
1,83 |
667 |
20 |
MS7 |
|
5 x 16 |
0,7 |
17,2 |
20,4 |
1,15 |
1035 |
25 |
MS9 |
|
5 x 25 |
0,9 |
21,4 |
24,8 |
0,727 |
1570 |
32 |
MS10 |
|
Nominal crosssectional area (mm²) |
Minimum number of wires in the conductor |
Maximum resistance of conductor at 20°C |
|||||||
|
Circular |
Circular Compacted |
Shaped |
Annealed copper conductor |
Aluminium or aluminium alloy conductor |
|||||
|
Cu |
Al |
Cu |
Al |
Cu |
Al |
Plain wires |
Metal-coated wires |
||
|
1,5 |
7 |
– |
6 |
– |
– |
– |
12,1 |
12,2 |
|
|
2,5 |
7 |
– |
6 |
– |
– |
– |
7,41 |
7,56 |
|
|
4 |
7 |
– |
6 |
– |
– |
– |
4,61 |
4,7 |
|
|
6 |
7 |
– |
6 |
– |
– |
– |
3,08 |
3,11 |
|
|
10 |
7 |
7 |
6 |
6 |
– |
– |
1,83 |
1,84 |
3,08 |
|
16 |
7 |
7 |
6 |
6 |
– |
– |
1,15 |
1,16 |
1,91 |
|
25 |
7 |
7 |
6 |
6 |
6 |
6 |
0,727 |
0,734 |
1,2 |
|
35 |
7 |
7 |
6 |
6 |
6 |
6 |
0,524 |
0,529 |
0,868 |
|
50 |
19 |
19 |
6 |
6 |
6 |
6 |
0,387 |
0,391 |
0,641 |
|
70 |
19 |
19 |
12 |
12 |
12 |
12 |
0,268 |
0,27 |
0,443 |
|
95 |
19 |
19 |
15 |
15 |
15 |
15 |
0,193 |
0,195 |
0,32 |
|
120 |
37 |
37 |
18 |
15 |
18 |
15 |
0,153 |
0,154 |
0,253 |
|
150 |
37 |
37 |
18 |
15 |
18 |
15 |
0,124 |
0,126 |
0,206 |
|
185 |
37 |
37 |
30 |
30 |
30 |
30 |
0,0991 |
0,1 |
0,164 |
|
240 |
37 |
37 |
34 |
34 |
34 |
34 |
0,0754 |
0,0762 |
0,125 |
|
300 |
61 |
61 |
34 |
34 |
34 |
34 |
0,0601 |
0,0607 |
0,1 |
|
400 |
61 |
61 |
53 |
53 |
53 |
53 |
0,047 |
0,0475 |
0,0778 |
| The above table is in accordance with BS EN 60228 | |||||||||
|
Conductor cross- sectional area |
Reference Method A |
Reference Method C |
Reference Method E |
|||
|
Enclosed in Conduit in thermally insulating wall etc. |
Clipped Direct, |
In free air or on a perforated cable tray etc, horizantal or vertical |
||||
|
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
|
|
1,5 |
18,5 |
16,5 |
24 |
22 |
26 |
23 |
|
2,5 |
25 |
22 |
33 |
30 |
36 |
32 |
|
4 |
33 |
30 |
45 |
40 |
49 |
42 |
|
6 |
42 |
38 |
58 |
52 |
63 |
54 |
|
10 |
57 |
51 |
80 |
71 |
86 |
75 |
|
16 |
76 |
68 |
107 |
96 |
115 |
100 |
|
25 |
99 |
89 |
138 |
119 |
149 |
127 |
|
35 |
121 |
109 |
171 |
147 |
185 |
158 |
|
50 |
145 |
130 |
209 |
179 |
225 |
192 |
|
70 |
183 |
164 |
269 |
229 |
289 |
246 |
|
95 |
220 |
197 |
328 |
278 |
352 |
298 |
|
120 |
253 |
227 |
382 |
322 |
410 |
346 |
|
150 |
290 |
259 |
441 |
371 |
473 |
399 |
|
185 |
329 |
295 |
506 |
424 |
542 |
456 |
|
240 |
386 |
346 |
599 |
500 |
641 |
538 |
|
300 |
442 |
396 |
693 |
576 |
741 |
621 |
|
400 |
– |
– |
803 |
667 |
865 |
741 |
| The above table is in accordance with BS 7671:2018 | ||||||
|
Conductor cross- sectional area |
Two core cable DC |
Two core cable,single phase AC |
Three or four core cable,three phase AC |
||||
|
mV/A/m |
mV/A/m |
mV/A/m |
|||||
|
1,5 |
31 |
31 |
27 |
||||
|
2,5 |
19 |
19 |
16 |
||||
|
4 |
12 |
12 |
10 |
||||
|
6 |
7,9 |
7,9 |
6,8 |
||||
|
10 |
4,7 |
4,7 |
4,0 |
||||
|
16 |
2,9 |
2,9 |
2,5 |
||||
|
r |
x |
z |
r |
x |
z |
||
|
25 |
1,85 |
1,85 |
0,160 |
1,90 |
1,60 |
0,140 |
1,65 |
|
35 |
1,35 |
1,35 |
0,155 |
1,35 |
1,15 |
0,135 |
1,15 |
|
50 |
0,98 |
0,99 |
0,155 |
1,00 |
0,86 |
0,135 |
0,87 |
|
70 |
0,67 |
0,67 |
0,150 |
0,69 |
0,59 |
0,130 |
0,60 |
|
95 |
0,49 |
0,50 |
0,150 |
0,52 |
0,43 |
0,130 |
0,45 |
|
120 |
0,39 |
0,40 |
0,145 |
0,42 |
0,34 |
0,130 |
0,37 |
|
150 |
0,31 |
0,32 |
0,145 |
0,35 |
0,28 |
0,125 |
0,30 |
|
185 |
0,25 |
0,26 |
0,145 |
0,29 |
0,22 |
0,125 |
0,26 |
|
240 |
0,195 |
0,20 |
0,140 |
0,24 |
0,175 |
0,125 |
0,21 |
|
300 |
0,155 |
0,16 |
0,140 |
0,21 |
0,140 |
0,120 |
0,185 |
|
400 |
0,120 |
0,13 |
0,140 |
0,190 |
0,115 |
0,120 |
0,165 |
| The above table is in accordance with BS 7671:2018 | |||||||