YMvK
0.6/1 kV XLPE insulated power cables
| -20/+90 °C | Flame Retardant IEC 60332-1-2 | Flame Retardant IEC 60332-3-24 |

Application
Installation in walls, on boards and in channels or embedded in plaster.
Construction
Cu/XLPE/PVC
1- Conductor: Copper
2-Insulation: XLPE
3- Filler : PVC
4- Outer sheath: PVC
Technical Data
Min. bending radius 15 x D
Max. operating temperature 90 ºC
Short circuit temperature: 250 ºC
Details
| Construction | Cu/XLPE/PVC |
|---|---|
| Standard | HD 604 PART 4 SECTION D |
|
Cross-section (mm²) |
Reaction To Fire classification |
Cross-section (mm²) |
Reaction To Fire classification |
|
2×1,5 |
Dca-s2,d2,a3 |
4×1,5 |
Dca-s2,d2,a3 |
|
2×2,5 |
Dca-s2,d2,a3 |
4×2,5 |
Dca-s2,d2,a3 |
|
2×4 |
Dca-s2,d2,a3 |
4×4 |
Dca-s2,d2,a3 |
|
2×6 |
Dca-s2,d2,a3 |
4×6 |
Dca-s2,d2,a3 |
|
2×10 |
Dca-s2,d2,a3 |
4 x 10 |
Dca-s2,d2,a3 |
|
2×16 |
Dca-s2,d2,a3 |
4 x 16 |
Dca-s2,d2,a3 |
|
2×25 |
Dca-s2,d2,a3 |
4×25 |
Dca-s2,d2,a3 |
|
2×35 |
Dca-s2,d2,a3 |
4×35 |
Dca-s2,d2,a3 |
|
2×50 |
Dca-s2,d2,a3 |
4×50 |
Dca-s2,d2,a3 |
|
2×70 |
Dca-s2,d2,a3 |
4×70 |
Dca-s2,d2,a3 |
|
4×95 |
Dca-s2,d2,a3 |
||
|
3×1,5 |
Dca-s2,d2,a3 |
4×120 |
Dca-s2,d2,a3 |
|
3×2,5 |
Dca-s2,d2,a3 |
4×150 |
Dca-s2,d2,a3 |
|
3×4 |
Dca-s2,d2,a3 |
||
|
3×6 |
Dca-s2,d2,a3 |
5×1,5 |
Dca-s2,d2,a3 |
|
3 x 10 |
Dca-s2,d2,a3 |
5×2,5 |
Dca-s2,d2,a3 |
|
3 x 16 |
Dca-s2,d2,a3 |
5×4 |
Dca-s2,d2,a3 |
|
3 x 25 |
Dca-s2,d2,a3 |
5×6 |
Dca-s2,d2,a3 |
|
3 x 35 |
Dca-s2,d2,a3 |
5 x 10 |
Dca-s2,d2,a3 |
|
3×50 |
Dca-s2,d2,a3 |
5 x 16 |
Dca-s2,d2,a3 |
|
3×70 |
Dca-s2,d2,a3 |
5 x 25 |
Dca-s2,d2,a3 |
|
3×95 |
Dca-s2,d2,a3 |
5 x 35 |
Dca-s2,d2,a3 |
|
3×120 |
Dca-s2,d2,a3 |
5×50 |
Dca-s2,d2,a3 |
|
3×150 |
Dca-s2,d2,a3 |
5×70 |
Dca-s2,d2,a3 |
|
5×95 |
Dca-s2,d2,a3 |
||
|
5×120 |
Dca-s2,d2,a3 |

|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under sheath |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
1×1,5 |
0,7 |
2,8 |
5,6 |
12,1 |
47 |
20S |
MS3 |
|
1×2,5 |
0,7 |
3,1 |
5,9 |
7,41 |
58 |
20S |
MS3 |
|
1×4 |
0,7 |
3,6 |
6,4 |
4,61 |
75 |
20S |
MS3 |
|
1×6 |
0,7 |
4,1 |
6,9 |
3,08 |
97 |
20S |
MS3 |
|
1×10 |
0,7 |
5,2 |
8,0 |
1,83 |
143 |
20S |
MS4 |
|
1×16 |
0,7 |
6,1 |
8,9 |
1,15 |
201 |
20S |
MS4 |
|
1×25 |
0,9 |
7,7 |
10,5 |
0,727 |
296 |
20S |
MS5 |
|
1×35 |
0,9 |
8,7 |
11,5 |
0,524 |
388 |
20S |
MS5 |
|
1×50 |
1 |
10,2 |
13,0 |
0,387 |
513 |
20S |
MS6 |
|
1×70 |
1,1 |
11,9 |
14,7 |
0,268 |
706 |
20 |
MS6 |
|
1×95 |
1,1 |
13,7 |
16,7 |
0,193 |
962 |
20 |
MS7 |
|
1×120 |
1,2 |
15,4 |
18,4 |
0,153 |
1189 |
25 |
MS8 |
|
1×150 |
1,4 |
17,1 |
20,3 |
0,124 |
1476 |
25 |
MS9 |
|
1×185 |
1,6 |
19,2 |
22,4 |
0,0991 |
1827 |
25 |
MS9 |
|
1×240 |
1,7 |
21,9 |
25,3 |
0,0754 |
2360 |
32 |
MS10 |
|
1×300 |
1,8 |
24,5 |
28,1 |
0,0601 |
2960 |
32 |
MS12 |
|
1×400 |
2 |
27,4 |
31,2 |
0,0470 |
3722 |
40 |
MS14 |
|
2×1,5 |
0,7 |
6,0 |
9,6 |
12,1 |
140 |
20S |
MS4 |
|
2×2,5 |
0,7 |
6,8 |
10,4 |
7,41 |
173 |
20S |
MS5 |
|
2×4 |
0,7 |
7,7 |
11,3 |
4,61 |
220 |
20S |
MS5 |
|
2×6 |
0,7 |
8,7 |
12,3 |
3,08 |
278 |
20S |
MS5 |
|
2×10 |
0,7 |
10,8 |
14,4 |
1,83 |
409 |
20S |
MS6 |
|
2×16 |
0,7 |
12,8 |
16,4 |
1,15 |
574 |
20 |
MS7 |
|
2×25 |
0,9 |
17,0 |
20,6 |
0,727 |
752 |
25 |
MS9 |
|
2×35 |
0,9 |
19,0 |
22,6 |
0,524 |
955 |
25 |
MS9 |
|
2×50 |
1 |
22,1 |
25,7 |
0,387 |
1240 |
32 |
MS11 |
|
2×70 |
1,1 |
25,5 |
29,1 |
0,268 |
1662 |
32 |
MS12 |
|
2×95 |
1,1 |
29,3 |
33,1 |
0,193 |
2233 |
40 |
MS14 |
|
2×120 |
1,2 |
32,7 |
36,9 |
0,153 |
2762 |
50S |
MS16 |
|
2×150 |
1,4 |
36,0 |
40,4 |
0,124 |
3384 |
50S |
MS16 |
|
2×185 |
1,6 |
40,7 |
45,3 |
0,0991 |
4229 |
50 |
MS18 |
|
2×240 |
1,7 |
46,1 |
51,1 |
0,0754 |
5407 |
63S |
MT9 |
|
2×300 |
1,8 |
51,5 |
56,9 |
0,0601 |
6767 |
63 |
MT9 |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under armour |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
3×1,5 |
0,7 |
6,5 |
10,1 |
12,1 |
157 |
20S |
MS4 |
|
3×2,5 |
0,7 |
7,3 |
10,9 |
7,41 |
198 |
20S |
MS5 |
|
3×4 |
0,7 |
8,3 |
11,9 |
4,61 |
258 |
20S |
MS5 |
|
3×6 |
0,7 |
9,3 |
12,9 |
3,08 |
333 |
20S |
MS6 |
|
3 x 10 |
0,7 |
11,6 |
15,2 |
1,83 |
498 |
20 |
MS7 |
|
3 x 16 |
0,7 |
13,8 |
17,4 |
1,15 |
710 |
20 |
MS7 |
|
3 x 25 |
0,9 |
18,2 |
21,8 |
0,727 |
997 |
25 |
MS9 |
|
3 x 35 |
0,9 |
20,4 |
24,0 |
0,524 |
1290 |
32 |
MS10 |
|
3×50 |
1 |
23,7 |
27,3 |
0,387 |
1691 |
32 |
MS11 |
|
3×70 |
1,1 |
27,4 |
31,2 |
0,268 |
2320 |
40 |
MS14 |
|
3×95 |
1,1 |
31,5 |
35,5 |
0,193 |
3146 |
40 |
MS14 |
|
3×120 |
1,2 |
35,1 |
39,3 |
0,153 |
3887 |
50S |
MS16 |
|
3×150 |
1,4 |
39,1 |
43,7 |
0,124 |
4861 |
50 |
MS18 |
|
3×185 |
1,6 |
43,8 |
48,6 |
0,0991 |
5993 |
50 |
MS20 |
|
3×240 |
1,7 |
49,6 |
54,8 |
0,0754 |
7707 |
63S |
MT9 |
|
3×300 |
1,8 |
55,4 |
61,0 |
0,0601 |
9664 |
63 |
MT10 |
|
4×1,5 |
0,7 |
7,2 |
10,8 |
12,1 |
181 |
20S |
MS5 |
|
4×2,5 |
0,7 |
8,1 |
11,7 |
7,41 |
232 |
20S |
MS5 |
|
4×4 |
0,7 |
9,2 |
12,8 |
4,61 |
306 |
20S |
MS6 |
|
4×6 |
0,7 |
10,4 |
14,0 |
3,08 |
400 |
20S |
MS6 |
|
4 x 10 |
0,7 |
13,0 |
16,6 |
1,83 |
605 |
20 |
MS7 |
|
4 x 16 |
0,7 |
15,4 |
19,0 |
1,15 |
872 |
25 |
MS8 |
|
4×25 |
0,9 |
20,2 |
23,8 |
0,727 |
1259 |
32 |
MS10 |
|
4×35 |
0,9 |
22,6 |
26,2 |
0,524 |
1650 |
32 |
MS11 |
|
4×50 |
1 |
26,4 |
30,2 |
0,387 |
2192 |
40 |
MS12 |
|
4×70 |
1,1 |
30,7 |
34,7 |
0,268 |
3052 |
40 |
MS14 |
|
4×95 |
1,1 |
35,0 |
39,2 |
0,193 |
4099 |
50S |
MS16 |
|
4×120 |
1,2 |
39,6 |
44,2 |
0,153 |
5166 |
50 |
MS18 |
|
4×150 |
1,4 |
43,5 |
48,3 |
0,124 |
6357 |
50 |
MS20 |
|
4×185 |
1,6 |
48,7 |
53,9 |
0,0991 |
7876 |
63S |
MT9 |
|
4×240 |
1,7 |
55,5 |
61,1 |
0,0754 |
10160 |
63 |
MT10 |
|
4×300 |
1,8 |
61,8 |
67,8 |
0,0601 |
12695 |
75S |
MT11 |
|
Nominal cross-section (mm²) |
Nominal Thickness of Insulation (mm) |
Approx. Diameter under armour |
Approximate overall diameter (mm) |
Max. Conductor DC resistance at 20 ºC (ohm/km) |
Approximate net weight (kg/km) |
GLAND |
Cable Cleats |
|
5×1,5 |
0,7 |
8,0 |
11,6 |
12,1 |
209 |
20S |
MS5 |
|
5×2,5 |
0,7 |
9,0 |
12,6 |
7,41 |
270 |
20S |
MS5 |
|
5×4 |
0,7 |
10,2 |
13,8 |
4,61 |
360 |
20S |
MS6 |
|
5×6 |
0,7 |
11,5 |
15,1 |
3,08 |
474 |
20S |
MS6 |
|
5 x 10 |
0,7 |
14,4 |
18,0 |
1,83 |
724 |
25 |
MS8 |
|
5 x 16 |
0,7 |
18,2 |
21,8 |
1,15 |
1047 |
25 |
MS9 |
|
5 x 25 |
0,9 |
22,3 |
25,9 |
0,727 |
1542 |
32 |
MS11 |
|
5 x 35 |
0,9 |
25,0 |
28,6 |
0,524 |
2021 |
32 |
MS12 |
|
5×50 |
1 |
29,4 |
33,4 |
0,387 |
2746 |
40 |
MS14 |
|
5×70 |
1,1 |
34,2 |
38,4 |
0,268 |
3798 |
50S |
MS16 |
|
5×95 |
1,1 |
39,1 |
43,7 |
0,193 |
5112 |
50 |
MS18 |
|
5×120 |
1,2 |
44,1 |
48,9 |
0,153 |
6382 |
63S |
MS20 |
|
5×150 |
1,4 |
48,5 |
53,7 |
0,124 |
7891 |
63S |
MT9 |
|
5×185 |
1,6 |
54,3 |
59,9 |
0,0991 |
9814 |
63 |
MT10 |
|
5×240 |
1,7 |
61,8 |
67,8 |
0,0754 |
12690 |
75S |
MT11 |
|
5×300 |
1,8 |
68,8 |
75,2 |
0,0601 |
15887 |
MT12 |
|
Nominal crosssectional area (mm²) |
Minimum number of wires in the conductor |
Maximum resistance of conductor at 20°C |
|||||||
|
Circular |
Circular Compacted |
Shaped |
Annealed copper conductor |
Aluminium or aluminium alloy conductor |
|||||
|
Cu |
Al |
Cu |
Al |
Cu |
Al |
Plain wires |
Metal-coated wires |
||
|
1,5 |
7 |
– |
6 |
– |
– |
– |
12,1 |
12,2 |
|
|
2,5 |
7 |
– |
6 |
– |
– |
– |
7,41 |
7,56 |
|
|
4 |
7 |
– |
6 |
– |
– |
– |
4,61 |
4,7 |
|
|
6 |
7 |
– |
6 |
– |
– |
– |
3,08 |
3,11 |
|
|
10 |
7 |
7 |
6 |
6 |
– |
– |
1,83 |
1,84 |
3,08 |
|
16 |
7 |
7 |
6 |
6 |
– |
– |
1,15 |
1,16 |
1,91 |
|
25 |
7 |
7 |
6 |
6 |
6 |
6 |
0,727 |
0,734 |
1,2 |
|
35 |
7 |
7 |
6 |
6 |
6 |
6 |
0,524 |
0,529 |
0,868 |
|
50 |
19 |
19 |
6 |
6 |
6 |
6 |
0,387 |
0,391 |
0,641 |
|
70 |
19 |
19 |
12 |
12 |
12 |
12 |
0,268 |
0,27 |
0,443 |
|
95 |
19 |
19 |
15 |
15 |
15 |
15 |
0,193 |
0,195 |
0,32 |
|
120 |
37 |
37 |
18 |
15 |
18 |
15 |
0,153 |
0,154 |
0,253 |
|
150 |
37 |
37 |
18 |
15 |
18 |
15 |
0,124 |
0,126 |
0,206 |
|
185 |
37 |
37 |
30 |
30 |
30 |
30 |
0,0991 |
0,1 |
0,164 |
|
240 |
37 |
37 |
34 |
34 |
34 |
34 |
0,0754 |
0,0762 |
0,125 |
|
300 |
61 |
61 |
34 |
34 |
34 |
34 |
0,0601 |
0,0607 |
0,1 |
|
400 |
61 |
61 |
53 |
53 |
53 |
53 |
0,047 |
0,0475 |
0,0778 |
| The above table is in accordance with BS EN 60228 | |||||||||
|
Conductor cross- sectional area |
Reference Method A |
Reference Method C |
Reference Method E |
|||
|
Enclosed in Conduit in thermally insulating wall etc. |
Clipped Direct, |
In free air or on a perforated cable tray etc, horizantal or vertical |
||||
|
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
1 two core cable, single-phase AC or DC (A) |
Three or four core cable, three-phase AC (A) |
|
|
1,5 |
18,5 |
16,5 |
24 |
22 |
26 |
23 |
|
2,5 |
25 |
22 |
33 |
30 |
36 |
32 |
|
4 |
33 |
30 |
45 |
40 |
49 |
42 |
|
6 |
42 |
38 |
58 |
52 |
63 |
54 |
|
10 |
57 |
51 |
80 |
71 |
86 |
75 |
|
16 |
76 |
68 |
107 |
96 |
115 |
100 |
|
25 |
99 |
89 |
138 |
119 |
149 |
127 |
|
35 |
121 |
109 |
171 |
147 |
185 |
158 |
|
50 |
145 |
130 |
209 |
179 |
225 |
192 |
|
70 |
183 |
164 |
269 |
229 |
289 |
246 |
|
95 |
220 |
197 |
328 |
278 |
352 |
298 |
|
120 |
253 |
227 |
382 |
322 |
410 |
346 |
|
150 |
290 |
259 |
441 |
371 |
473 |
399 |
|
185 |
329 |
295 |
506 |
424 |
542 |
456 |
|
240 |
386 |
346 |
599 |
500 |
641 |
538 |
|
300 |
442 |
396 |
693 |
576 |
741 |
621 |
|
400 |
– |
– |
803 |
667 |
865 |
741 |
| The above table is in accordance with BS 7671:2018 | ||||||
|
Conductor cross- sectional area |
Two core cable DC |
Two core cable,single phase AC |
Three or four core cable,three phase AC |
||||
|
mV/A/m |
mV/A/m |
mV/A/m |
|||||
|
1,5 |
31 |
31 |
27 |
||||
|
2,5 |
19 |
19 |
16 |
||||
|
4 |
12 |
12 |
10 |
||||
|
6 |
7,9 |
7,9 |
6,8 |
||||
|
10 |
4,7 |
4,7 |
4,0 |
||||
|
16 |
2,9 |
2,9 |
2,5 |
||||
|
r |
x |
z |
r |
x |
z |
||
|
25 |
1,85 |
1,85 |
0,160 |
1,90 |
1,60 |
0,140 |
1,65 |
|
35 |
1,35 |
1,35 |
0,155 |
1,35 |
1,15 |
0,135 |
1,15 |
|
50 |
0,98 |
0,99 |
0,155 |
1,00 |
0,86 |
0,135 |
0,87 |
|
70 |
0,67 |
0,67 |
0,150 |
0,69 |
0,59 |
0,130 |
0,60 |
|
95 |
0,49 |
0,50 |
0,150 |
0,52 |
0,43 |
0,130 |
0,45 |
|
120 |
0,39 |
0,40 |
0,145 |
0,42 |
0,34 |
0,130 |
0,37 |
|
150 |
0,31 |
0,32 |
0,145 |
0,35 |
0,28 |
0,125 |
0,30 |
|
185 |
0,25 |
0,26 |
0,145 |
0,29 |
0,22 |
0,125 |
0,26 |
|
240 |
0,195 |
0,20 |
0,140 |
0,24 |
0,175 |
0,125 |
0,21 |
|
300 |
0,155 |
0,16 |
0,140 |
0,21 |
0,140 |
0,120 |
0,185 |
|
400 |
0,120 |
0,13 |
0,140 |
0,190 |
0,115 |
0,120 |
0,165 |
| The above table is in accordance with BS 7671:2018 | |||||||